| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
1 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
2 |
2 SETS #500 MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
1 NEW PNL |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER (CELLAR) CELLAR SVC SWITCHES RACEWAY NOT GROUNDED 250.92A |
RSLV |
08/30/2018 |
08/30/2018 |
11/19/2018 |
| |
| 002 |
(999) |
OTHER (CELLAR) CELLAR SVC SWITCHES RACEWAY NOT CONTINUOUS 250.64C |
RSLV |
08/30/2018 |
08/30/2018 |
11/19/2018 |
| |
| 003 |
(999) |
OTHER (CELLAR) CELLAR SVC SWITCHES NEU NOT GROUNDED 250.28 |
RSLV |
08/30/2018 |
08/30/2018 |
10/26/2018 |
| |
| 004 |
(999) |
OTHER (CELLAR) CELLAR SVC SWITCHES NOT GROUNDED 250.24 C |
RSLV |
08/30/2018 |
08/30/2018 |
10/26/2018 |
| |
| 005 |
(999) |
OTHER (CELLAR) CELLAR WATER METER JUMPER NOT NOT PROPERLY SIZE 250.66 |
RSLV |
08/30/2018 |
08/30/2018 |
10/26/2018 |
| |
| 006 |
(999) |
OTHER (CELLAR) CELLAR WATER METER GND LOOSE 250. |
RSLV |
08/30/2018 |
08/30/2018 |
10/26/2018 |
| |
| 007 |
(999) |
OTHER (CELLAR) CELLAR COMMUNICATION BAR NOT INSTALL AT SVC AREA 250.94 |
RSLV |
08/30/2018 |
08/30/2018 |
11/19/2018 |
| |
| 008 |
(211) |
RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED (GROUND FLOOR) GND FL RECEPT OUTLETS NOT GROUNDED 250.146 |
RSLV |
08/30/2018 |
08/30/2018 |
11/19/2018 |
| |
| 009 |
(999) |
OTHER (GROUND FLOOR) GND FL KITCHEN RECPT OUTLETS DEFECTIVE 110.2 |
RSLV |
08/30/2018 |
08/30/2018 |
10/26/2018 |
| |
| 010 |
(999) |
OTHER (GROUND FLOOR) GND FL KITCHEN AND BAR RECEPT NOT GFCI 210.8 |
RSLV |
08/30/2018 |
08/30/2018 |
11/19/2018 |
| |
| 011 |
(999) |
OTHER (GROUND FLOOR) ALL PNL CKT NOT GROUPED 210.4D |
RSLV |
08/30/2018 |
08/30/2018 |
10/26/2018 |
| |
| 012 |
(999) |
OTHER (GROUND FLOOR) ALL PNL CKT MULTI CKT NEED TWO POLE BREAKERS 210.4B |
RSLV |
08/30/2018 |
08/30/2018 |
11/19/2018 |
| |
| 013 |
(999) |
OTHER (GROUND FLOOR) GND FL KITCHEN RACEWAY INSTALL IN DUCK HOOD 410.10 |
RSLV |
08/30/2018 |
08/30/2018 |
11/19/2018 |