BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B425128
Premises: 207 KINGSBOROUGH 2 WALK BROOKLYN BIN: 3324602     Block: 1344   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 219 KINGSBOROUGH 2ND WALK Census Tract:   307 Health Area:  5200
CELLAR TO ROOF Admin Area:   B - BROOKLYN Inspection Area:   E
BROOKLYN, NY 11233 Community Board:   308
Special Place Name:   KINGSBOROUGH HOUSES BUILDING #5
DOB Cross Street(s):   PACIFIC STREET,    BERGEN STREET
Status:   C - JOB IS SIGNED OFF 05/07/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/08/2017 11:35 AM
Application Entered:   03/08/2017 Job Start Date:   03/08/2017
Last Change:   05/07/2018 Job End Date:   06/30/2017
Appointment Status:   
Last Inspection By:   JEROME BLACK       On     05/04/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  

License #: 011240 Licensee Name: CRAIG GILSTON
Firm: 000591 Firm Name: GILSTON ELEC'L CONTNG LLC
Firm Phone: 212-410-7800  Firm Address: 338 EAST 95TH STREET NEW YORK NY 10128 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $50.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: NYC HOUSING AUTHORITY
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS            14             
GND            10             
002                       
003                       
004                       
005                       
006                       
007                       
Buildings Total         52                
Total Units : 52 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice:  
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  KINGSBOROUGH HOUSES BUILDING #5

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B425128
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/04/2018 05/07/2018 JKJ C (29) (0) Y
INSPECTION COMMENTS: THIS JOB IS GOOD




If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order