BIS Menu  |  Comments  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B423351
Premises: 991 OCEAN AVENUE BROOKLYN BIN: 3425744     Block: 5206   Lot: 50
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 991 OCEAN AV Census Tract:   516.01 Health Area:  7210
8 FLLOR Admin Area:   B - BROOKLYN Inspection Area:   K
BROOKLYN, NY 11226 Community Board:   314
Related Job Number:    320915140
DOB Cross Street(s):   DITMAS AVENUE,    NEWKIRK AVENUE
Status:   C - JOB IS SIGNED OFF 09/21/2018 Balance Paid By Owner
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/01/2017 1:22 PM
Application Entered:   02/01/2017 Job Start Date:   02/01/2017
Last Change:   09/21/2018 Job End Date:   01/15/2018
Appointment Status:   
Last Inspection By:   DALTON HENLON       On     08/31/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011485 Licensee Name: BENJAMIN DREBIN
Firm: 002950 Firm Name: ACCURATE ELEC'L CORP.
Firm Phone: 718-606-9181  Firm Address: 11-07 43RD ROAD LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
2 - TEMPORARY CONSTRUCTION
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
6 - GENERAL WIRING
7 - HVAC WIRING
8 - BOILER/BURNER WIRING
Total Fee:  $1,875.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ABE BATESH
Owner Business Name: ABCO
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  400AMP
D. 601 Up to 1200 AMPS  1  800AMP
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  25  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  3  3 SET 500,000
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  25  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  1  400 AMP PANEL
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    20  15                 
001  LOBBY  22  12  22         
002  A-D  45  44  36  36     
003  A-D  45  44  36  36     
004  A-D  45  44  36  36     
005  A-D  45  44  36  36     
006  A-D  45  44  36  36     
007  A-D  45  44  36  36     
008  A-B  22  40  32  22     
Buildings Total 334  331  56  257  260     56     39      
Total Units : 1333 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 25 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 26 - Removed Meters 0 = Total Meters 26

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 02/01/2017 Notice: 1 - FIRST NOTICE 08/20/2018
Power Issued: 02/01/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  Y1A2I3R4- SERVICE 8 FLOOR

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B423351
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/17/2018 08/20/2018 SGY V (110) (7)
INSPECTION COMMENTS: INSPECTION COMPLETED. OBJECTIONS ISSUED.
 
(2) 08/31/2018 08/31/2018 DAH C R (41) (0)
INSPECTION COMMENTS: THE VIOLATIONS ARE RESOLVED

OBJECTION FOR APPLICATION #: B423351
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS) (ART. 314.20) SET BACK (MICROWAVE OUTLET)
RSLV 08/17/2018 08/17/2018 08/31/2018
 
002 (999) OTHER
(ALL FLOORS) (ART. 250.140) DRYER OUTLET (4 PLUG RECEPTACLE)
RSLV 08/17/2018 08/17/2018 08/31/2018
 
003 (999) OTHER
(BASEMENT) (ART. 250.92) SERVICE EQUIPMENT NOT BONDED TOGETHER
RSLV 08/17/2018 08/17/2018 08/31/2018
 
004 (999) OTHER
(BASEMENT) (ART. 250.66) SIZE GROUNDING CONDUCTOR (LINE SIDE)
RSLV 08/17/2018 08/17/2018 08/31/2018
 
005 (999) OTHER
(BASEMENT) (ART. 350.60) EGC NOT PROVIDED FOR COMPACTOR MOTOR
RSLV 08/17/2018 08/17/2018 08/31/2018
 
006 (999) OTHER
(BASEMENT)(ART. 350.10) LFMC NOT PROVIDED FOR WET LOCATION (BOILER ROOM,4-WATER PUMPS)
RSLV 08/17/2018 08/17/2018 08/31/2018
 
007 (999) OTHER
(ROOF)(ART. 430.52) POWER FOR ELEVATOR DOES NOT MATCH WITH SPECIFICATION(DISCONNECT)
RSLV 08/17/2018 08/17/2018 08/31/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Comments  |  Electrical Inspection Work Order  |  Back