| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
1 |
1-30 A |
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
1 |
|
| D. 601 Up to 1200 AMPS |
1 |
1-800A |
| E. Over 1200 AMPS |
3 |
4-3000A, 1-1200A |
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
306 |
1 SET #6,305 SET#2 |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
1 |
1 SET 4/0 |
| D. Over 250 MCM |
61 |
32 50 KCMIL,20-600, 6-350 |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
305 |
1 PH 100A |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
9 |
8-100A,1-225A |
| D. 3 Phase Over 225 AMPS |
12 |
6-400,2-600,2-800,2-1200 |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER (ROOF)ROOF GENERATOR, AND ATS ROOM PLAQUES NOT PROVIDED FOR SWITCHES 230.2 |
RSLV |
01/17/2018 |
01/17/2018 |
08/17/2018 |
| |
| 002 |
(999) |
OTHER (ROOF)ROOF GENERATOR, AND ATS ROOM SWITCHES ARC FLASH HAZARD NOT PROVIDED110.16 |
RSLV |
01/17/2018 |
01/17/2018 |
08/17/2018 |
| |
| 003 |
(999) |
OTHER (ROOF) ROOF ATS ROOM 1ST SWITCH BONDING NOT SIZE PROPERLY 250.102 |
RSLV |
01/17/2018 |
01/17/2018 |
08/17/2018 |
| |
| 004 |
(999) |
OTHER (ROOF) ROOF GENERATOR ROOM SWITCH NEU NOT PROPERLY SIZE 220.61 |
RSLV |
01/17/2018 |
01/17/2018 |
08/17/2018 |
| |
| 005 |
(999) |
OTHER (ROOF) ROOF ATS ROOM SWITCH CKT NOT GROUPED 210.4D |
RSLV |
01/17/2018 |
01/17/2018 |
08/17/2018 |
| |
| 006 |
(999) |
OTHER (ROOF) ROOF GFCI NEED BUBBLE COVER 406.8 B |
RSLV |
01/17/2018 |
01/17/2018 |
08/17/2018 |
| |
| 007 |
(999) |
OTHER (FLOOR: 024) 024 APT KITCHEN COUNTER TOP RECEPT AT STOVE 110.2 |
RSLV |
05/01/2018 |
05/01/2018 |
08/17/2018 |
| |
| 008 |
(999) |
OTHER (FLOOR: 024) 024 APT 2412 HOT NEU REV 110.2 |
RSLV |
05/01/2018 |
05/01/2018 |
08/17/2018 |
| |
| 009 |
(999) |
OTHER (FLOOR: 024) 024 APT 2409 PNL NOT LABEL 408.4 |
RSLV |
05/01/2018 |
05/01/2018 |
08/17/2018 |
| |
| 010 |
(999) |
OTHER (FLOOR: 024) 024 APT 2410 KITCHEN COUNTER TOP NOT TR 408.11 |
RSLV |
05/01/2018 |
05/01/2018 |
08/17/2018 |
| |
| 011 |
(211) |
RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED (ALL FLOORS) THROUGHOUT RECEPT OUTLETS NOT GROUNDED 250.146 |
RSLV |
05/01/2018 |
05/01/2018 |
08/17/2018 |
| |
| 012 |
(999) |
OTHER (ALL FLOORS) (ART. 440.22(A)) ALL APT. AC UNITS OCP (MAX 15A) |
RSLV |
05/23/2018 |
05/23/2018 |
08/17/2018 |
| |
| 013 |
(999) |
OTHER (ALL FLOORS) (ART. 645.15) ALL AV CABINETS NOT BONDED |
RSLV |
05/23/2018 |
05/23/2018 |
08/17/2018 |
| |
| 014 |
(999) |
OTHER (ALL FLOORS) (ART. 314.20) ALL APT. SET BACK (MICROWAVE OUTLET) |
RSLV |
05/23/2018 |
05/23/2018 |
08/17/2018 |
| |
| 015 |
(999) |
OTHER (ALL FLOORS) (ART. 210.12(B)) ALL APT. SD NOT AFCI PROTECTED |
RSLV |
05/23/2018 |
05/23/2018 |
08/17/2018 |
| |
| 016 |
(999) |
OTHER (ALL FLOORS)(ART. 300.10) LOOSE CONTINUITY (ALL LOCKNUTS LOOSE IN PANEL) |
RSLV |
05/23/2018 |
05/23/2018 |
08/17/2018 |
| |
| 017 |
(999) |
OTHER (ALL FLOORS) (ART. 110.2) BREAKERS NOT FOR USE (PANELS) |
RSLV |
05/23/2018 |
05/23/2018 |
08/17/2018 |
| |
| 018 |
(999) |
OTHER (ALL FLOORS)(ART. 200.6(A)) IDENTIFICATION FOR WHITE CONDUCTOR (ALL PANELS) |
RSLV |
05/23/2018 |
05/23/2018 |
08/17/2018 |
| |
| 019 |
(999) |
OTHER (ALL FLOORS)(ART. 250.118) DEFECTIVE WIRING (ALL MC CABLE FOR AC UNITS CUT OFFGROUND) |
RSLV |
05/23/2018 |
05/23/2018 |
08/17/2018 |
| |
| 020 |
(999) |
OTHER (ALL FLOORS)(ART. 210.70(A3)) MINIMUM SERVICE FOR STORAGE, LIGHT FIXTURE (APT.2410, 2310) |
RSLV |
05/23/2018 |
05/23/2018 |
08/17/2018 |
| |
| 021 |
(999) |
OTHER (ALL FLOORS)(ART. 210.52(C)) LOCATION COUNTER TOP GFCI (APT. 2311 AND 2411) |
RSLV |
05/23/2018 |
05/23/2018 |
08/17/2018 |
| |
| 022 |
(999) |
OTHER (ALL FLOORS) (ART. 410.42) ALL HALLWAY WALL LIGHT FIXTURES LOOSE EGC |
RSLV |
05/23/2018 |
05/23/2018 |
08/17/2018 |
| |
| 023 |
(999) |
OTHER (ALL FLOORS)(ART. 424.19) ALL LAUNDRY ROOM HEATERS WITHOUT DISCONNECTING |
RSLV |
05/23/2018 |
05/23/2018 |
08/17/2018 |
| |
| 024 |
(999) |
OTHER (ROOF) (ART. 250.148) ALL SPLICE BOXES NOT BONDED |
RSLV |
05/23/2018 |
05/23/2018 |
08/17/2018 |
| |
| 025 |
(999) |
OTHER (ROOF) (ART. 250.118(6)) LFMC FROM GENERATOR TO SWITCH LOOSE EGC |
RSLV |
05/23/2018 |
05/23/2018 |
08/17/2018 |
| |
| 026 |
(999) |
OTHER (ROOF) (ART. 250.8(A)) SCREW FOR GROUND LUG (ALL AC UNITS) |
RSLV |
05/23/2018 |
05/23/2018 |
08/17/2018 |