BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B422050
Premises: 280 ST MARKS AVENUE BROOKLYN BIN: 3424489     Block: 1152   Lot: 35
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 280 ST MARKS AV Census Tract:   205 Health Area:  2710
. Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11238 Community Board:   308
Related Job Number:    320597564
DOB Cross Street(s):   VANDERBILT AVENUE,    UNDERHILL AVENUE
Status:   C - JOB IS SIGNED OFF 02/22/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/30/2016 1:43 PM
Application Entered:   12/30/2016 Job Start Date:   12/30/2016
Last Change:   02/22/2018 Job End Date:   12/30/2017
Appointment Status:   
Last Inspection By:   SCHUSZTER, NORBET       On     02/21/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012297 Licensee Name: JOHN AHRENS
Firm: 004066 Firm Name: TUXEDO ELEC'L CONTR'G INC
Firm Phone: 718-786-0384  Firm Address: 10-32 47TH ROAD LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $290.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: DAVID BERGER
Owner Business Name: ESCORIAL 280 SMA, LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  2  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 11/25/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B422050
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/26/2017 09/27/2017 CJH N (31) (0) Y
INSPECTION COMMENTS: NO SHOW
 
(2) 10/18/2017 10/18/2017 DIT N (20) (0) Y
INSPECTION COMMENTS: CALLED CONTRACTOR NO SHOW
 
(3) 11/02/2017 11/03/2017 DIT J (37) (0) Y
INSPECTION COMMENTS: NO ACCESS TO ELEVATOR PIT .(FULL INSPECTION REQUIRED) .
 
(4) 11/22/2017 11/25/2017 EID V (100) (4)
INSPECTION COMMENTS: INSPECTION COMPLETED. OBJ. ISSUED
 
(5) 02/21/2018 02/22/2018 NRS C R (49) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED.

OBJECTION FOR APPLICATION #: B422050
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 13) THE CONDUCTORS FEEDING THE MOTORS ARE NOT OF PROPER SIZE
(ROOF) #12 CONDUCTOR FEEDING A 17.90A RATED MOTOR.
RSLV 11/22/2017 11/22/2017 02/21/2018
 
002 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
(ROOF)MTR. RM.: ELEV.DISCS. AND CAR LT. DISC. EGC TERMINATED AT ISOLATEDNEUTRAL BAR/ NOT BONDED
RSLV 11/22/2017 11/22/2017 02/21/2018
 
003 (245) NEUTRAL IS FUSED
(ROOF) BOTH CAR LT. DISC (ART. 240.22)
RSLV 11/22/2017 11/22/2017 02/21/2018
 
004 (999) OTHER
(ROOF)MTR. RM.: ELEV. DISCS.: EGC CONDUCTORS NOT SZED AS PER 250.122
RSLV 11/22/2017 11/22/2017 02/21/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order