BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B421073
Premises: 401 STATE STREET BROOKLYN BIN: 3000564     Block: 172   Lot: 50
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 401 STATE ST Census Tract:   41 Health Area:  2400
CELLAR, 1ST - 4TH FL, ROOF Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11217 Community Board:   302
Special Place Name:   STATE OF BEING
DOB Cross Street(s):   BOND STREET,    NEVINS STREET
Status:   C - JOB IS SIGNED OFF 08/26/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/06/2016 2:27 PM
Application Entered:   12/06/2016 Job Start Date:   12/06/2016
Last Change:   08/26/2019 Job End Date:   12/31/2017
Appointment Status:   
Last Inspection By:   JOHN HUGHES       On     08/26/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011456 Licensee Name: RALPH OCCHIPINTI
Firm: 000064 Firm Name: ADCO ELEC'L CORP
Firm Phone: 718-494-4400  Firm Address: 201 EDWARD CURRY AVENUE STATEN ISLAND NY 10314 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
L - LIGHTING WORK
Total Fee:  $2,159.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  321402558
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: KELLY MERRYMAN
Owner Business Name: STATE OF BEING LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  1  1600A
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  6  
B. Over #2 to 1/0  3  
C. Over 1/0 to 250 MCM  5  
D. Over 250 MCM  3  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  7  60A - 200A
D. 3 Phase Over 225 AMPS  3  1600A, 600A, 400A
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    45  100    66  157  12  52         
001    107  88    57  391  10         
002    44  96    56  170         
003    45  79    58  173         
004    39  42    27  146         
ROF    12    33  10  58         
Buildings Total 292  414    266  1070     126           
Total Units : 2168 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 12/06/2016 Notice: 1 - FIRST NOTICE 08/14/2019
Power Issued: 12/06/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  JH JOB #160212 - FURNISH AND INSTALL LIGHTING FIXTURES AND LIGHTING CONTROLS, DEVICES AND 120V SERVICE SWITCHBOARD AND POWER EQUIPMENT. NEW CON ED METER / SERVICE WORK.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B421073
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/15/2019 07/15/2019 CJH V (136) (7)
INSPECTION COMMENTS: CONTRACTOR NEED TO FILE FOR THE CORRECT AMOUNT OF PANELS, FEEDER CONDUCTORS.
 
(2) 08/14/2019 08/14/2019 DJG V R (59) (1)
INSPECTION COMMENTS: FAIL. OBJECTION ISSUED.
 
(3) 08/26/2019 08/26/2019 JGX C R (15) (0)
INSPECTION COMMENTS: THE OUTSTANDING OBJECTION HAS BEEN SATISFIED WITH THE FILING OF APP B00214111 AS PER INSPECTOR'S REQUIREMENT. THIS JOB IS GOOD.

OBJECTION FOR APPLICATION #: B421073
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS) THROUGHOUT GFCI NOT APPROVED 110.2/.3
RSLV 07/15/2019 07/15/2019 08/14/2019
 
002 (999) OTHER
(ALL FLOORS) THROUGHOUT PNL CKT NOT GROUPED 210.4D
RSLV 07/15/2019 07/15/2019 08/14/2019
 
003 ( 12) SERVICE CONDUCTORS ARE NOT OF THE PROPER SIZE
(CELLAR) SVC SWITCH CONDUCTORS NOT SIZE PROPERLY 23023/.42 AMEN
RSLV 07/15/2019 07/15/2019 08/14/2019
 
004 (998) SEE ECB VIOLATION
(CELLAR) SVC SWITCH CONDUCTORS NOT FULL COPPER 240.4
RSLV 07/15/2019 07/15/2019 08/14/2019
 
005 (999) OTHER
(CELLAR) CELLAR FIRE PUMP FUSES NOT SIZE CORRECT 430.250/695.4 B
RSLV 07/15/2019 07/15/2019 08/14/2019
 
006 (999) OTHER
(CELLAR) CELLAR SVC SWITCHES PLAQUES NOT PROVIDED 230.3
RSLV 07/15/2019 07/15/2019 08/14/2019
 
007 (999) OTHER
(ROOF) ROOF AC UNITS NOT LABEL 110.22
RSLV 07/15/2019 07/15/2019 08/14/2019
 
008 (999) OTHER
(ALL FLOORS)CONTRACTOR NEED TO AMEND APP FOR ALL FEEDER WIRES AND PANELSINCLUDING LUTRON PANELS.
RSLV 08/14/2019 08/14/2019 08/26/2019



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back