BIS Menu  |  Elevators  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B420838
Premises: 510 FLATBUSH AVENUE BROOKLYN BIN: 3397203     Block: 5024   Lot: 53
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 510 FLATBUSH AV Census Tract:   327 Health Area:  4800
BUILDING Admin Area:   B - BROOKLYN Inspection Area:   G
BROOKLYN, NY 11225 Community Board:   309
Related Job Number:    320374064
DOB Cross Street(s):   EMPIRE BOULEVARD,    LEFFERTS AVENUE
Status:   C - JOB IS SIGNED OFF 01/20/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/30/2016 4:18 PM
Application Entered:   11/30/2016 Job Start Date:   11/30/2016
Last Change:   01/20/2017 Job End Date:   08/30/2017
Appointment Status:   
Last Inspection By:   MOSES, DANIEM       On     01/17/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011592 Licensee Name: MARK OSTROVSKY
Firm: 001987 Firm Name: OM ELECTRIC, INC
Firm Phone: 212-944-7799  Firm Address: 262 WEST 38TH STREET, RM 1202 NEW YORK NY 10018 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $1,386.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (2  Stores, 51 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: 31 LINCOLN RD DEV
Authorized Representative:  THOMAS ANDERSON
Relationship To Owner:   AUTHORIZED REPRESENTATIVE


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  60 AMP
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  ONLY 1 600 A
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  3  4 # 3 AWG
B. Over #2 to 1/0  1  4 # 1/0 AWG
C. Over 1/0 to 250 MCM  6  4 - 3/0 AWG
D. Over 250 MCM  4  4-350 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  4  4 - 100 AMP
D. 3 Phase Over 225 AMPS  4  3 - 400 AMP, 1 - 600 AMP
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS              50  28     
001                     
002                     
003                     
004                     
005                     
006                     
007                     
008                     
009                     
ROF                  16  250     
Buildings Total              50     314      
Total Units : 364 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 12/20/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  THIS APPLICATION IS IN CONJUNCTION WITH APPLICATION BEC # B397627.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B420838
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/19/2016 12/20/2016 CCH V (60) (2)
INSPECTION COMMENTS: JOB FAIL
 
(2) 01/17/2017 01/18/2017 DNM C R (55) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED.

OBJECTION FOR APPLICATION #: B420838
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(CELLAR) 60 A NO WATER GROUND
RSLV 12/19/2016 12/19/2016 01/17/2017
 
002 (999) OTHER
(CELLAR) 60 A FEEDERS PASS THROUGH PANEL 230.7
RSLV 12/19/2016 12/19/2016 01/17/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.