| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
1 |
4-500MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (BASEMENT)3 1/2'' RACEWAY PENETRATED WALLS NOT FIRE STOPPED. ART. 300.21 |
RSLV |
04/24/2017 |
04/24/2017 |
03/01/2019 |
| |
| 002 |
( 40) |
LOCKNUTS ARE MISSING OR LOOSE (BASEMENT)2'' LOCKNUT ON PIPE AT PULLED BOX NOT PROPERLY INSTALLED. ART.300.11 |
RSLV |
04/24/2017 |
04/24/2017 |
01/02/2018 |
| |
| 003 |
( 41) |
LOCKNUTS ARE NOT MADE UP TIGHT (BASEMENT) 3 1/2 '' LOCKNUTS AT PULL BOX LOOSE. ART. 300.11 |
RSLV |
04/24/2017 |
04/24/2017 |
01/02/2018 |
| |
| 004 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) (BASEMENT) 3 1/2''RACEWAY NOT SUPPORTED AT PULL BOX. |
RSLV |
04/24/2017 |
04/24/2017 |
01/02/2018 |
| |
| 005 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) (BASEMENT) 2''RACEWAY NOT SUPPORTED AT PULL BOX. |
RSLV |
04/24/2017 |
04/24/2017 |
01/02/2018 |
| |
| 006 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER (BASEMENT) THERE IS NO BONDING IN END BOX. ART. 250.92 A |
RSLV |
01/02/2018 |
01/02/2018 |
03/01/2019 |
| |
| 007 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (BASEMENT) 3 INCH COUPLING CUT AND USED AS LOCKNUTS IN PULL BOX. |
RSLV |
01/02/2018 |
01/02/2018 |
03/01/2019 |