NYC Department of Buildings
Electrical Application Details for App #: B420150
Premises: 351 9 STREET BROOKLYN BIN: 3022136     Block: 1005   Lot: 7502
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 357 9TH ST Census Tract:   137 Health Area:  4600
BASEMENT Admin Area:   B - BROOKLYN Inspection Area:   F
BROOKLYN, NY 11215 Community Board:   306
Special Place Name:   PROSPECT PARK YMCA
DOB Cross Street(s):    5 AVENUE,    6 AVENUE
Status:   C - JOB IS SIGNED OFF 03/02/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/15/2016 8:51 PM
Application Entered:   11/15/2016 Job Start Date:   11/17/2016
Last Change:   03/02/2019 Job End Date:   12/17/2016
Appointment Status:   
Last Inspection By:   SERGIY MOTORIN       On     03/01/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012107 Licensee Name: EMIL KRSLOVIC
Firm: 004422 Firm Name: EDM ELECTRIC INC
Firm Phone: 718-956-6165  Firm Address: 32-51 56TH STREET WOODSIDE NY 11377 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $115.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   HEALTH CLUB
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: YMCA OF GREATER NY
Authorized Representative:  COREY BEDFORD
Relationship To Owner:   FACILITY OPERATIONS MANAG


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  4-500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 01/03/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INSTALLING NEW CONDUIT AND FEEDERS IN VAULT BELOW SIDEWALK TO REROUTE EXISTING BUILDING PANEL ELECTRICAL FEEDERS.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B420150
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/24/2017 04/26/2017 CJE V (72) (5)
INSPECTION COMMENTS: INSPECTION FAIL
 
(2) 01/02/2018 01/03/2018 JGX V Y (44) (2)
INSPECTION COMMENTS: SEE OBJECTIONS.
 
(3) 03/01/2019 03/02/2019 SGY C R (15) (0)
INSPECTION COMMENTS: OBJECTIONS RESOLVED. OK TO CLOSE. NEW APPLICATION #B00112230I1EL.

OBJECTION FOR APPLICATION #: B420150
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(BASEMENT)3 1/2'' RACEWAY PENETRATED WALLS NOT FIRE STOPPED. ART. 300.21
RSLV 04/24/2017 04/24/2017 03/01/2019
 
002 ( 40) LOCKNUTS ARE MISSING OR LOOSE
(BASEMENT)2'' LOCKNUT ON PIPE AT PULLED BOX NOT PROPERLY INSTALLED. ART.300.11
RSLV 04/24/2017 04/24/2017 01/02/2018
 
003 ( 41) LOCKNUTS ARE NOT MADE UP TIGHT
(BASEMENT) 3 1/2 '' LOCKNUTS AT PULL BOX LOOSE. ART. 300.11
RSLV 04/24/2017 04/24/2017 01/02/2018
 
004 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(BASEMENT) 3 1/2''RACEWAY NOT SUPPORTED AT PULL BOX.
RSLV 04/24/2017 04/24/2017 01/02/2018
 
005 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(BASEMENT) 2''RACEWAY NOT SUPPORTED AT PULL BOX.
RSLV 04/24/2017 04/24/2017 01/02/2018
 
006 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(BASEMENT) THERE IS NO BONDING IN END BOX. ART. 250.92 A
RSLV 01/02/2018 01/02/2018 03/01/2019
 
007 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(BASEMENT) 3 INCH COUPLING CUT AND USED AS LOCKNUTS IN PULL BOX.
RSLV 01/02/2018 01/02/2018 03/01/2019