| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
2 |
2 X 4-#2 |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
2 |
CKT |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (FLOOR: 005)KITCHEN AREA RECEP OUTLET BOX INSTALLED IN COMBUSTIBLE MATERIAL (ART314.20) |
OPEN |
12/08/2020 |
12/08/2020 |
|
| |
| 002 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (FLOOR: 005)EGC'S NOT BONDED/TERMINATED IN SPLICE BOX ENCLOSURE. ART. 250.148(C) |
OPEN |
12/08/2020 |
12/08/2020 |
|
| |
| 003 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (FLOOR: 005)PANEL MULTIWIRE BRANCH CKT DOES NOT SIMULTANEOUSLY TRIP (ART 210.4 |
OPEN |
12/08/2020 |
12/08/2020 |
|
| |
| 004 |
(211) |
RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED (FLOOR: 005)THROUGHOUT RECEP AND SWITCHES ARE NOT PROPERLY BONDED (ART 250.146)HALLWAYS |
OPEN |
12/08/2020 |
12/08/2020 |
|
| |
| 005 |
(236) |
OUTSIDE A/C DISCONNECT NOT ACCESSIBLE (FLOOR: 005) HVAC UNITS NOT ACCESSIBLE AS PER CODE |
OPEN |
12/08/2020 |
12/08/2020 |
|
| |
| 006 |
(307) |
NO RECEPTACLE OUTLET WITHIN 25 FEET FOR HVAC EQUIPMENT (FLOOR: 005)NO RECEP OUTLET WITHIN 25 FEET FOR HVAC EQUIPMENT (ART 210.63) |
OPEN |
12/08/2020 |
12/08/2020 |
|
| |
| 007 |
(999) |
OTHER (FLOOR: 005)SIGNAGE HAS NOT BEEN PROVIDED FOR ELECTRICAL ROOM/CLOSETS (AMEND110.25) |
OPEN |
12/08/2020 |
12/08/2020 |
|
| |
| 008 |
( 16) |
DEFECTIVE LIGHTING FIXTURES ARE IN USE (ALL FLOORS) UL LISTING NEEDED FOR LIGHTS INSTALLED |
OPEN |
12/08/2020 |
12/08/2020 |
|