BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Property Profile  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B419277
Premises: 351 9 STREET BROOKLYN BIN: 3022136     Block: 1005   Lot: 7502
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 357 9 ST Census Tract:   137 Health Area:  4600
NA Admin Area:   B - BROOKLYN Inspection Area:   F
BROOKLYN, NY 11215 Community Board:   306
DOB Cross Street(s):    5 AVENUE,    6 AVENUE
Status:   C - JOB IS SIGNED OFF 12/13/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/27/2016 6:18 PM
Application Entered:   10/27/2016 Job Start Date:   10/28/2016
Last Change:   12/13/2018 Job End Date:   11/28/2016
Appointment Status:   
Last Inspection By:   NAJI PHILLIIPS       On     12/12/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012446 Licensee Name: ROOPCHAND SINGH
Firm: 004601 Firm Name: ELECTROTEC OF NY ELECL IN
Firm Phone: 212-785-0065  Firm Address: 58-30 64TH STREET MASPETH NY 11378 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
9 - OTHER
Total Fee:  $58.75
Other Work:   RETROFIT AND/OR REPLA
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   GYMNASIUM
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: NA NA
Owner Business Name: YMCA OF GREATER NY PROSPE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND            85             
Buildings Total         85                
Total Units : 85 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 11/23/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  RETROFIT AND/OR REPLACE LIGHT FIXTURES ONLY. NOT BRANCH CIRCUIT WIRING.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B419277
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/12/2018 09/13/2018 NJP V (65) (3)
INSPECTION COMMENTS: CORRECT OBJECTION. STORE: YMCA
 
(2) 11/16/2018 11/19/2018 OSZ N (15) (0) Y
INSPECTION COMMENTS: YMCA MANAGEMENT WAS UNAWARE OF INSPECTION AND DID NOT GRANT ACCESS.
 
(3) 11/23/2018 11/23/2018 NJP V R (30) (1)
INSPECTION COMMENTS: CORRECT OBJECTION.
 
(4) 12/12/2018 12/13/2018 NJP C R (25) (0)
INSPECTION COMMENTS: OBJECTION RESOLVED.

OBJECTION FOR APPLICATION #: B419277
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS) FIXTURE NOT PROPERLY SUPPORTED (ART 410.36)
RSLV 09/12/2018 09/12/2018 11/23/2018
 
002 (999) OTHER
(ALL FLOORS) ARMORED CABLES ARE NOT PROPERLY TERMINATED (ART 320.40)
RSLV 09/12/2018 09/12/2018 11/23/2018
 
003 (999) OTHER
(ALL FLOORS) ARMORED CABLES ARE INSTALLED EXPOSED
RSLV 09/12/2018 09/12/2018 11/23/2018
 
004 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
(ALL FLOORS)THROUGHOUT ARMORED CABLES ARE NOT PROPERLY SUPPORTED/SECURED INCEILINGS (ART 320)
RSLV 11/23/2018 11/23/2018 12/12/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Property Profile  |  Electrical Inspection Work Order  |  Back