Electrical Application Details for App #: B417992
Premises: 212 FLATBUSH AVENUE BROOKLYN BIN: 3018493     Block: 931   Lot: 24
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 212 FLATBUSH AV Census Tract:   129.02 Health Area:  2600
BSMT Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11217 Community Board:   306
Special Place Name:   SERVICE WORK
DOB Cross Street(s):   DEAN STREET,    BERGEN STREET
Status:   C - JOB IS SIGNED OFF 05/24/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/28/2016 1:58 PM
Application Entered:   09/28/2016 Job Start Date:   09/29/2016
Last Change:   05/24/2017 Job End Date:   12/31/2016
Appointment Status:   
Last Inspection By:   JOHN, CHARLES       On     01/26/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011918 Licensee Name: LUKASZ TYKA
Firm: 003946 Firm Name: CENTRUM ELECTRIC CORP
Firm Phone: 917-543-9736  Firm Address: 12 LOMBARDY STREET BROOKLYN NY 11222 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $305.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (1  Stores, 4 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: 212 FLATBUSH LLC
Authorized Representative:  SAL LAVORE
Relationship To Owner:   MEMBER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  5  100AMPS
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  400AMPS
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  3/0 AWG
D. Over 250 MCM  1  500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 5 #4-Wire 0 #10-Wire 1
Existing Meters 6 + New Meters 6 - Removed Meters 6 = Total Meters 6

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 09/28/2016 Notice: C - CALL TO OFFICE 12/28/2016
Power Issued: 09/28/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  WORK ON SERVICE ONLY

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B417992
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/18/2016 10/19/2016 CJH N (41) (0) Y
INSPECTION COMMENTS: NO ACCESS
 
(2) 11/01/2016 11/02/2016 CCH V (45) (3)
INSPECTION COMMENTS: JOB FAIL
 
(3) 11/16/2016 11/18/2016 HRB N (15) (0) Y
INSPECTION COMMENTS: NO SHOW NO ACCESS
 
(4) 12/27/2016 12/28/2016 CJE V X (55) (1)
INSPECTION COMMENTS: CONTRACTOR NO SHOW,
 
(5) 01/26/2017 01/31/2017 CJH C R (28) (0)
INSPECTION COMMENTS: OBJECTION REMOVED

OBJECTION FOR APPLICATION #: B417992
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(BASEMENT) 400 A SERVICE
RSLV 11/01/2016 11/01/2016 01/26/2017
 
002 ( 42) BUSHINGS ARE MISSING OR LOOSE
(BASEMENT) BONDING SCREWS
RSLV 11/01/2016 11/01/2016 01/26/2017
 
003 (999) OTHER
(BASEMENT) NO LIGHT NEAR SERVICE 110.26
RSLV 11/01/2016 11/01/2016 01/26/2017
 
004 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(BASEMENT) #8 G.E.C. INSTALLED EXPOSED. ART. 250.64(B)
RSLV 12/27/2016 12/27/2016 01/26/2017