Electrical Application Details for App #: B417947
Premises: 190 PLYMOUTH STREET BROOKLYN BIN: 3000037     Block: 31   Lot: 7503
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 205 WATER ST Census Tract:   21 Health Area:  1000
7&8 FLOOR Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11201 Community Board:   302
DOB Cross Street(s):   JAY STREET,    BRIDGE STREET
Status:   C - JOB IS SIGNED OFF 08/07/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/28/2016 10:59 AM
Application Entered:   09/28/2016 Job Start Date:   09/29/2016
Last Change:   08/07/2017 Job End Date:   10/12/2016
Appointment Status:   
Last Inspection By:   JEFFERSON, CHARLES       On     08/04/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009365 Licensee Name: MICHAEL SCHONDORF
Firm: 000995 Firm Name: MICHAEL SCHONDORF, INC
Firm Phone: 212-244-4312  Firm Address: 545 WEST 45TH STREET..6F NEW YORK NY 10036 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $185.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BJARKE INGELS
Owner Business Name: -----
Authorized Representative:  BJARKE INGELS
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  2   ONE 70 AMP AND ONE 200 A
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
007    59  32    59  15         
008    23  10    23         
Buildings Total 82  42    82     18           
Total Units : 232 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 07/21/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B417947
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/29/2017 06/30/2017 FDY V (60) (3)
INSPECTION COMMENTS: INSPECTION COMPLETED. A MINOR WORK APPLICATION WAS FILED FOR THE UPPER BATHROOM IN THIS APARTMENT FOR A BATHROOM THAT IS STILL UNDER CONSTRUCTION BY A DIFFERENT CONTRACTOR.
 
(2) 07/17/2017 07/18/2017 DAH N (15) (0) Y
INSPECTION COMMENTS: NO ACCESS DUE TO TECHNICAL DIFFICULTY WITH THE COMPUTER , THE OWNER LEFT EARLIER
 
(3) 07/21/2017 07/21/2017 FDY V Y (49) (1)
INSPECTION COMMENTS: THIS CONTRACTOR SHARED SOME ELECTRICAL WORK OUT OF THE SAME PANEL WITH GMJ ELECTRICAL CONTRACTORS WHO DID MORE THAN MINOR WORK AND NEEDS TO AMEND BOTH B430717 AND B430715 FROM TWO MINOR WORK APPS TO ONE REGULAR APPLICATION.
 
(4) 08/04/2017 08/07/2017 CJE C R (48) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED.

OBJECTION FOR APPLICATION #: B417947
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 008)210.8 GFCI'S OUTSIDE NOT INSTALLED PROPERLY. GFCI OUTSIDE ON ROOFNOT WORKING.
RSLV 06/29/2017 06/29/2017 07/21/2017
 
002 (999) OTHER
(FLOOR: 008)210.52 (C) (4) PENISULA WITH A RANGE NEEDS ANOTHER GFCI.
RSLV 06/29/2017 06/29/2017 07/21/2017
 
003 (999) OTHER
(FLOOR: 008) 110.12 MC CABLE IN CLOSET NOT SPICED WITHIN A BOX.
RSLV 06/29/2017 06/29/2017 08/04/2017
 
004 (999) OTHER
(FLOOR: 002)210.8 (A)(1) THE BATHROOM UPSTAIRS DOES NOT HAVE A GFCI INSIDE THEBATHROOM. THERE IS ONE NEARBY IN THE BEDROOM.
RSLV 07/21/2017 07/21/2017 08/04/2017