BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B417493
Premises: 147 7 AVENUE BROOKLYN BIN: 3024853     Block: 1069   Lot: 7
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 147 7TH AV Census Tract:   157 Health Area:  4500
ALL FLOORS Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11215 Community Board:   306
DOB Cross Street(s):   CARROLL STREET,    GARFIELD PLACE
Status:   C - JOB IS SIGNED OFF 02/22/2023
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/20/2016 12:59 PM
Application Entered:   09/20/2016 Job Start Date:   09/20/2016
Last Change:   02/22/2023 Job End Date:   09/19/2017
Appointment Status:   
Last Inspection By:   ADAM ADAMSKI       On     10/20/2022      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012754 Licensee Name: ALEXANDER MERZLYAK
Firm: 003893 Firm Name: L&B ELEC'L INTERNATIONAL
Firm Phone: 347-295-0380  Firm Address: 150-50 11TH AVENUE WHITESTONE NY 11357 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $93.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (2  Stores, 1 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: CHONG CHA CHANG
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS      10           
GND              21         
001    60    20  10               
002    50    20  15               
Buildings Total 115    50  30       27           
Total Units : 222 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 10/04/2022
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B417493
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/13/2022 09/14/2022 JKJ J (26) (0) Y
INSPECTION COMMENTS: JOB IN PROGRESS NEW INSPECTION NEEDED
 
(2) 09/22/2022 09/22/2022 SWR N (30) (0) Y
INSPECTION COMMENTS: CALLED THE CONTRACTOR. NO ONE ANSWERED THE CALL. NO ACCESS FOR VISUAL INSPECTION. OFFICE DIRECTION OK TO PROCEED.
 
(3) 10/03/2022 10/04/2022 DWB V (38) (2)
INSPECTION COMMENTS: INSPECTION COMPLETE, OBJECTION ISSUED.
 
(4) 10/20/2022 10/21/2022 ASK C R (28) (0)
INSPECTION COMMENTS: PASS. INSPECTION COMPLETED. OBJECTION CHECKED ONLY.

OBJECTION FOR APPLICATION #: B417493
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS)GND FLR-BOXES SET BACK (COMB FLUSH, NON-COMB ) (406.4 REC)314.20/ WITH WOOD AND WALL FABRIC/ THRU-OUT
RSLV 10/03/2022 10/03/2022 10/20/2022
 
002 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS)LED TRANSFORMERS MUST BE ACCESSIBLE AFTER INSTALLATION 410.144/ NOTACCESSIBLE AT HAIR DRESSER CABINET.
RSLV 10/03/2022 10/03/2022 10/20/2022



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back