BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B417482
Premises: 160 7 AVENUE BROOKLYN BIN: 3020688     Block: 966   Lot: 42
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 160 7 AV Census Tract:   157 Health Area:  4500
BASEMENT Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11215 Community Board:   306
DOB Cross Street(s):   GARFIELD PLACE,    1 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/20/2016 10:34 AM
Application Entered:   09/20/2016 Job Start Date:   09/20/2016
Last Change:   08/22/2025 Job End Date:   10/10/2016
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   ROBINSON HEATH       On     10/07/2016      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 010910 Licensee Name: DAVID HARARI
Firm: 004667 Firm Name: SEGA ELECTRIC LLC
Firm Phone: 347-512-7985  Firm Address: 72-40 MAIN STREET FLUSHING NY 11367 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $48.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: GAVRIEL PLAZA 2
Authorized Representative:  YUDA ATON
Relationship To Owner:   MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  PANEL+MAIN
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 1 #10-Wire 0
Existing Meters 8 + New Meters 1 - Removed Meters 1 = Total Meters 8

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 09/20/2016 Notice: 1 - FIRST NOTICE 10/07/2016
Power Issued: 09/20/2016 Response:  

Follow-Up:
Contractor's Comments:  REACTIVATE METER FOR THE STORE(RESTAURANT)

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B417482
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/07/2016 10/07/2016 HRB V (55) (2)
INSPECTION COMMENTS: FAILED

OBJECTION FOR APPLICATION #: B417482
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(BASEMENT) IN BOTH SERVICES SWITCHES
OPEN 10/07/2016 10/07/2016
 
002 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(BASEMENT)MAIN GROUND AND GROUND ROD NOT GOING TO BOTH SERVICE SWITCHES
OPEN 10/07/2016 10/07/2016