BIS Menu  |  Elevators  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B416250
Premises: 491 KEAP STREET BROOKLYN BIN: 3413996     Block: 2371   Lot: 21
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 500 METROPOLITAN AV Census Tract:   513
CELLAR Admin Area:   B - BROOKLYN Inspection Area:   A
BROOKLYN, NY 11211 Community Board:   301
Related Job Number:    320373751
DOB Cross Street(s):   MEEKER AVENUE,    UNION AVENUE
Status:   C - JOB IS SIGNED OFF 08/24/2018
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   08/24/2016 Job Start Date:   08/15/2016
Last Change:   08/24/2018 Job End Date:   08/15/2018
Appointment Status:   
Last Inspection By:   DALTON HENLON       On     08/22/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010255 Licensee Name: THOMAS ZIMMERMAN
Firm: 004025 Firm Name: FIRST QUALITY ELECT CORP
Firm Phone: 718-797-3518  Firm Address: 75 HUNGTINGTON STREET BROOKLYN NY 11231 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $4,338.00
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   HOTEL
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   54027     Submittal #: 16A0303  
Owner / Occup: MAYER CHETRIT
Owner Business Name: THE CHETRIT GROUP
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  60 AMP FIRE ALARM
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  600 AMP FIRE PUMP
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  6  3-1600A,2-2000A,1-1200A
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  #6 FIRE ALARM
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  3/0 FIRE PUMP
D. Over 250 MCM  25  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 59 #4-Wire 0 #10-Wire 7
Existing Meters 0 + New Meters 66 - Removed Meters 0 = Total Meters 66

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 08/24/2016 Notice: 1 - FIRST NOTICE 08/16/2018
Power Issued: 08/24/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  FEEDERS & BRANCH CIRCUIT WIRING FILED UNDER APPLICATION#B415861

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B416250
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/15/2018 08/16/2018 DAH V (40) (3)
INSPECTION COMMENTS: DEFECTIVE WIRING ARE IN PLACED ; PLEASE SEE APPS B00067145 & B0006744
 
(2) 08/22/2018 08/22/2018 DAH C R (35) (0)
INSPECTION COMMENTS: THE JOB IS OK

OBJECTION FOR APPLICATION #: B416250
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(BASEMENT)PARALLEL RACEWAYS OF 2000 A FDRS ( NO EGC ) AS PER ARTL .250 . 122
RSLV 08/15/2018 08/15/2018 08/22/2018
 
002 (999) OTHER
(BASEMENT)EGC IS NOT PROVIDED IN (2) 800 A RACEWAYS TO TRAN "S" CAB. ARTL .250 . 122
RSLV 08/15/2018 08/15/2018 08/22/2018
 
003 (999) OTHER
(BASEMENT)JOCKEY PUMP IS MOT AS PER ARTL 420 .250 ,430 . 251 & 695 . 6 (B) ,695 . 6 (F)
RSLV 08/15/2018 08/15/2018 08/22/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.