| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
4 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
4 |
4 SET OF #2 THHN |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
3 |
3 PANELS |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (ALL FLOORS) ALL NEUTRALS FROM AC FEEDERS TO ROOF BEING USED AS EGC |
OPEN |
07/13/2017 |
07/13/2017 |
|
| |
| 002 |
(132) |
EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED (ROOF)SERVICE GFCI PICKING UP NEUTRAL FROM GROUND BAR FROM 1ST FLOOR ACDISC/SW |
RSLV |
07/13/2017 |
07/13/2017 |
08/17/2017 |
| |
| 003 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (ROOF)1ST FLOOR AC DISC/SW 2 WIRES ON SAME LUG OF ONE OF THE PHASES FROMFEEDER |
RSLV |
07/13/2017 |
07/13/2017 |
08/17/2017 |
| |
| 004 |
( 19) |
DEFECTIVE WIRING IS IN USE (ROOF) SERVICE GFCI BEING FED FROM 1ST FLOOR AC DISC/SW |
RSLV |
07/13/2017 |
07/13/2017 |
08/17/2017 |
| |
| 005 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (ROOF) AC DISC/SW NO EGC PROVIDED FROM EACH APT FEEDERS |
OPEN |
07/13/2017 |
07/13/2017 |
|
| |
| 006 |
(999) |
OTHER (ALL FLOORS)ROOF AC UNITS FEEDER LACK MECHANICAL CONTINUITY OF METAL RACEWAY NOCHANGE OVER 300.12 |
OPEN |
08/17/2017 |
08/17/2017 |
|
| |
| 007 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (ROOF)ROOF RACEWAY FOR GFCI RECEPT OUTLET INSTALL DIRECTLY ON ROOF 300. |
OPEN |
08/17/2017 |
08/17/2017 |
|
| |
| 008 |
( 37) |
MOTOR DISCONNECT SWITCH HAS NOT BEEN PROVIDED (ROOF)ROOF AC UNITS NOT PROPERLY MARK PERMANENT MARKER IN USED 110.2 |
OPEN |
08/17/2017 |
08/17/2017 |
|