BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B416044
Premises: 2060 PACIFIC STREET BROOKLYN BIN: 3038694     Block: 1439   Lot: 37
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 2060 PACIFIC ST Census Tract:   303 Health Area:  5200
PACIFIC STREET Admin Area:   B - BROOKLYN Inspection Area:   E
BROOKLYN, NY 11233 Community Board:   316
DOB Cross Street(s):   HOWARD AVENUE,    SARATOGA AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/20/2016 12:18 PM
Application Entered:   08/20/2016 Job Start Date:   08/21/2016
Last Change:   08/22/2025 Job End Date:   12/19/2016
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   JOHN, CHARLES       On     08/17/2017      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  Y - PARTLY REMOVED

License #: 009520 Licensee Name: NORMAN H WEISS
Firm: 000186 Firm Name: ATN ELECTRIC CORP
Firm Phone: 718-347-6200  Firm Address: 247-73 JAMAICA AVENUE BELLEROSE NY 11426 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $257.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   C - Three Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOEY YAAKOVZADEH
Owner Business Name: JOEY YAAKOVZADEH
Authorized Representative:  NORMAN WEISS
Relationship To Owner:   ELECTRIC CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  4  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  4  4 SET OF #2 THHN
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  3  3 PANELS
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    12  10    12             
001    20  18    12  20         
001  20  18    12  20         
002    20  18    13  20     
003    20  19    13  20         
Buildings Total 92  83    55  92            
Total Units : 333 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 4 #4-Wire 0 #10-Wire 0
Existing Meters 2 + New Meters 4 - Removed Meters 2 = Total Meters 4

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 08/20/2016 Notice: 1 - FIRST NOTICE 08/17/2017
Power Issued: 08/20/2016 Response:  

Follow-Up:
Contractor's Comments:  TO REWIRE THE WHOLE HOUSE NEW FOUR METER SERVICE UNDER GROUND

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B416044
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/21/2017 06/22/2017 DNM N (17) (0) Y
INSPECTION COMMENTS: ELECTRICIAN SAYS HE WAS UNAWARE OF INSPECTION.
 
(2) 07/13/2017 07/13/2017 JTE V (60) (5)
INSPECTION COMMENTS: INSPECTION FAIL, SEE OBJECTION DETAILS
 
(3) 08/17/2017 08/17/2017 CJH V Y (66) (3)
INSPECTION COMMENTS: FAIL

OBJECTION FOR APPLICATION #: B416044
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(ALL FLOORS) ALL NEUTRALS FROM AC FEEDERS TO ROOF BEING USED AS EGC
OPEN 07/13/2017 07/13/2017
 
002 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
(ROOF)SERVICE GFCI PICKING UP NEUTRAL FROM GROUND BAR FROM 1ST FLOOR ACDISC/SW
RSLV 07/13/2017 07/13/2017 08/17/2017
 
003 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ROOF)1ST FLOOR AC DISC/SW 2 WIRES ON SAME LUG OF ONE OF THE PHASES FROMFEEDER
RSLV 07/13/2017 07/13/2017 08/17/2017
 
004 ( 19) DEFECTIVE WIRING IS IN USE
(ROOF) SERVICE GFCI BEING FED FROM 1ST FLOOR AC DISC/SW
RSLV 07/13/2017 07/13/2017 08/17/2017
 
005 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(ROOF) AC DISC/SW NO EGC PROVIDED FROM EACH APT FEEDERS
OPEN 07/13/2017 07/13/2017
 
006 (999) OTHER
(ALL FLOORS)ROOF AC UNITS FEEDER LACK MECHANICAL CONTINUITY OF METAL RACEWAY NOCHANGE OVER 300.12
OPEN 08/17/2017 08/17/2017
 
007 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ROOF)ROOF RACEWAY FOR GFCI RECEPT OUTLET INSTALL DIRECTLY ON ROOF 300.
OPEN 08/17/2017 08/17/2017
 
008 ( 37) MOTOR DISCONNECT SWITCH HAS NOT BEEN PROVIDED
(ROOF)ROOF AC UNITS NOT PROPERLY MARK PERMANENT MARKER IN USED 110.2
OPEN 08/17/2017 08/17/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back