BIS Menu  |  Electrical Applications  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B415937
Premises: 26 LAWTON STREET BROOKLYN BIN: 3073414     Block: 3229   Lot: 10
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 26 LAWTON ST Census Tract:   393 Health Area:  3200
BSMT TO 5 FLOOR Admin Area:   B - BROOKLYN Inspection Area:   E
BROOKLYN, NY 11221 Community Board:   304
Related Job Number:    320623722
DOB Cross Street(s):   BROADWAY,    BUSHWICK AVENUE
Status:   C - JOB IS SIGNED OFF 06/15/2020
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/17/2016 8:09 PM
Application Entered:   08/17/2016 Job Start Date:   08/17/2016
Last Change:   06/15/2020 Job End Date:   05/30/2017
Appointment Status:   
Last Inspection By:   DAMISO COOTE       On     06/15/2020      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011018 Licensee Name: LUIS M JIMENEZ
Firm: 002356 Firm Name: L J ELEC'L SERV. INC.
Firm Phone: 718-239-8970  Firm Address: 1408 ROSEDALE AVENUE BRONX NY 10472 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $374.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: GEORGIO KELESIDIS
Owner Business Name: NIKKI SUITES LLC
Authorized Representative:  GEORGIO KELESIDIS
Relationship To Owner:   GENERAL CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  1 - 200 AMP
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  7  7 - 6#3
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  8  8 - 12 CIRC.
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001  BSMT  12  10    12  12             
001  1R  18             
001  2F  18             
002  1F  18             
002  2R  18             
003  3F  18             
003  3R  18             
004  4F  12  26  12             
Buildings Total 58  144  15  54  58                
Total Units : 329 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 8 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 8 - Removed Meters 0 = Total Meters 8

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 08/17/2016 Notice: 1 - FIRST NOTICE 09/16/2019
Power Issued: 08/17/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  NEW SERVICE METER 120/208 VOLT., 100 AMP, SINGLE PHASE AND WIRING FOR LIGHT AND POWER

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B415937
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/31/2019 08/15/2019 JKJ J (20) (0) Y
INSPECTION COMMENTS: 110.22A 300.11 240.3 2504A 408.4 ALL AREAS
 
(2) 09/16/2019 09/16/2019 JKJ V (45) (2)
INSPECTION COMMENTS: JOB IN PROGRESS OBJECTIONS EXISTING SEE COMMENTS
 
(3) 06/15/2020 06/15/2020 DIT C R (41) (0)
INSPECTION COMMENTS: OBJECTIONS RESOLVED

OBJECTION FOR APPLICATION #: B415937
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(ROOF) 240.3 AC ALL APTS OVERFUSED
RSLV 09/16/2019 09/16/2019 06/15/2020
 
002 ( 8) CONDUIT IS NOT PROPERLY SUPPORTED (TYPE:IMC)
(ROOF) 342.30 PIPES ON ROOFTOP AC
RSLV 09/16/2019 09/16/2019 06/15/2020



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Applications  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back