Electrical Application Details for App #: B415331
Premises: 117 LIVINGSTON STREET BROOKLYN BIN: 3425971     Block: 154   Lot: 40
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 415 RED HOOK LANE Census Tract:   37
CELLAR Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11201 Community Board:   302
Related Job Number:    320626747
DOB Cross Street(s):       BOERUM PLACE
Status:   C - JOB IS SIGNED OFF 07/23/2018
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   08/05/2016 Job Start Date:   07/25/2016
Last Change:   07/23/2018 Job End Date:   12/31/2017
Appointment Status:   
Last Inspection By:   OSCAR ZELAYA       On     12/21/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012245 Licensee Name: PETER ARANA
Firm: 003988 Firm Name: SANT-TEC ELECTRIC INC
Firm Phone: 718-644-7645  Firm Address: 516 INDUSTRIAL LOOP 2ND FL STATEN ISLAND NY 10309 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $2,073.00
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (2  Stores, 108 Apartments)
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   53793     Submittal #: 15A0582  
Owner / Occup: TIMOTHY QUINLAN
Owner Business Name: RED HOOK LANE LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  1-30A
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  4  1-800A,3-1200A
E. Over 1200 AMPS  1  1-2500A
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  10  10-750KCMIL
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 109 #4-Wire 0 #10-Wire 4
Existing Meters 0 + New Meters 113 - Removed Meters 0 = Total Meters 113

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 08/05/2016 Notice: 1 - FIRST NOTICE 12/12/2017
Power Issued: 08/05/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  ......ELECTRICAL SERVICE

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B415331
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/09/2017 08/09/2017 EBA V (150) (2)
INSPECTION COMMENTS: FAIL
 
(2) 12/12/2017 12/12/2017 EID V R (60) (1)
INSPECTION COMMENTS: INSPECTION COMPLETED. OBJ. ISSUED.
 
(3) 12/21/2017 12/23/2017 OSZ C R (35) (0)
INSPECTION COMMENTS: JOB IS OK.

OBJECTION FOR APPLICATION #: B415331
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(BASEMENT)GROUNDING CONDUCTORS NOT TERMINATED ON NEUTRAL BAR ,ALL SWITCHES250 24.C.
RSLV 08/09/2017 08/09/2017 12/12/2017
 
002 (999) OTHER
(BASEMENT)NOT AS PER DRAWING, NEUTRAL DISK LINK,EXIT THAT LEADS INTO ROOM,PUSH BAR ON DOOR, 110.2.B.
RSLV 08/09/2017 08/09/2017 12/12/2017
 
003 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
(ROOF) BULKHEAD: NO GND PROVIDED TO GENERATOR.
RSLV 12/12/2017 12/12/2017 12/21/2017