BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B415078
Premises: 109 SOUTH 5 STREET BROOKLYN BIN: 3063433     Block: 2443   Lot: 34
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 109 S 5 ST Census Tract:   549
BASEMENT Admin Area:   B - BROOKLYN Inspection Area:   B
BROOKLYN, NY 11249 Community Board:   301
DOB Cross Street(s):   BERRY STREET,    BEDFORD AVENUE
Status:   C - JOB IS SIGNED OFF 09/06/2016
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   08/01/2016 Job Start Date:   08/01/2016
Last Change:   09/06/2016 Job End Date:   08/01/2016
Appointment Status:   
Last Inspection By:   BANYA, E       On     08/31/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010593 Licensee Name: JOSE A MARENGO
Firm: 002839 Firm Name: ECS ELEC'L CONTG SERV INC
Firm Phone: 718-484-8884  Firm Address: 435 AUSTIN PLACE, SUITE E BRONX NY 10455 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $1,709.00
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   53596     Submittal #: 16A0236  
Owner / Occup:
Owner Business Name: MEADOW PARTNERS
Authorized Representative:  PETER ANDRESEN
Relationship To Owner:   P.M


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  3  30A F.A
B. 101 Up to 200 AMPS  2  1-200A
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  1  1-800A
E. Over 1200 AMPS  1  1-3000A
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  3  #12
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  #3/0
D. Over 250 MCM  10  2-600MCM 8-500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  1-200A 1-100A
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 2 #4-Wire 0 #10-Wire 2
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 08/01/2016 Notice: 1 - FIRST NOTICE 08/12/2016
Power Issued: 08/01/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  ADVISORY BOARD JOB

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B415078
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/12/2016 08/12/2016 EBA V (105) (6)
INSPECTION COMMENTS: FAIL
 
(2) 08/31/2016 08/31/2016 EBA C R (45) (0)
INSPECTION COMMENTS: VIOLATIONS REMOVED

OBJECTION FOR APPLICATION #: B415078
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(BASEMENT) PANIC BARS ON DOORS 110.26.C.2.
RSLV 08/12/2016 08/12/2016 08/31/2016
 
002 (999) OTHER
(BASEMENT) S/S #2 NEUTRAL NOT BONDED 250.28
RSLV 08/12/2016 08/12/2016 08/31/2016
 
003 (999) OTHER
(BASEMENT)GROUNDING CONDUIT NOT CONTINIOUS AT GROUND BAR AND WATER MAIN250.64.C.
RSLV 08/12/2016 08/12/2016 08/31/2016
 
004 (999) OTHER
(BASEMENT) 2- 200 AMP S/S GROUND UNDER SIZED 250.66.
RSLV 08/12/2016 08/12/2016 08/31/2016
 
005 (999) OTHER
(BASEMENT) WATER METER JUMPER 250.53.D.1.
RSLV 08/12/2016 08/12/2016 08/31/2016
 
006 (999) OTHER
(BASEMENT) DOUBLE LUGGING AT GROUND BAR 110.14.A.
RSLV 08/12/2016 08/12/2016 08/31/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.