Electrical Application Details for App #: B414339
Premises: 491 KEAP STREET BROOKLYN BIN: 3413996     Block: 2371   Lot: 21
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 500 METROPOLITAN AV Census Tract:   513 Health Area:  0700
ENTIRE Admin Area:   B - BROOKLYN Inspection Area:   A
BROOKLYN, NY 11211 Community Board:   301
Related Job Number:    320373751
DOB Cross Street(s):   MEEKER AVENUE,    UNION AVENUE
Status:   C - JOB IS SIGNED OFF 07/23/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/14/2016 5:58 PM
Application Entered:   07/14/2016 Job Start Date:   07/14/2016
Last Change:   07/23/2018 Job End Date:   07/14/2018
Appointment Status:   
Last Inspection By:   WEISBART, F.       On     07/23/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010255 Licensee Name: THOMAS ZIMMERMAN
Firm: 004025 Firm Name: FIRST QUALITY ELECT CORP
Firm Phone: 718-797-3518  Firm Address: 75 HUNGTINGTON STREET BROOKLYN NY 11231 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $1,415.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MEYER CHETRIT
Owner Business Name: THE CHETRIT GROUP
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  11  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 07/09/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B414339
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/09/2018 07/09/2018 OSZ V (55) (15)
INSPECTION COMMENTS: ELEVATOR E WAS NOT INSPECTED, IT WAS NOT IN SERVICE AT TIME OF INSPECTION. ELEVATOR MOTORS WERE ALSO NOT INSPECTED. OBJECTIONS WERE ISSUED.
 
(2) 07/23/2018 07/23/2018 FWE C R (35) (0)
INSPECTION COMMENTS: OK

OBJECTION FOR APPLICATION #: B414339
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (308) CONDUCTORS ARE NOT PROPERLY INSTALLED/TERMINATED
(ALL FLOORS)IN ALL CONTROL PANELS EGC IS DOUBLE LUGGED. ART. 110.14(A)
RSLV 07/09/2018 07/09/2018 07/23/2018
 
002 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(BASEMENT)ELEVATOR F, AND E LIGHTING DISCO'S ARE OVER FUSED, 30 AMPS ON #12AWG. ART. 240.3
RSLV 07/09/2018 07/09/2018 07/23/2018
 
003 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(BASEMENT)SMALL SERVICE ELEVATOR OVER FUSED AT 60 AMP MAX 30 AMP. ART. 240.3
RSLV 07/09/2018 07/09/2018 07/23/2018
 
004 ( 16) DEFECTIVE LIGHTING FIXTURES ARE IN USE
(BASEMENT)ELEVATORS C AND ONE NEXT TO IT, A AND B HAVE DEFECTIVE LIGHTING ATTHE TOP OF CAR. ART. 110.2(A)
RSLV 07/09/2018 07/09/2018 07/23/2018
 
005 ( 17) DEFECTIVE SWITCHES ARE IN USE
(BASEMENT) LIGHTS INSIDE ELEVATOR (C) DEFECTIVE. ART. 620.53
RSLV 07/09/2018 07/09/2018 07/23/2018
 
006 (188) MEANS OF POWER DISCONNECT NOT PROVIDED AS PER CODE
(BASEMENT) DISCO'S FOR RETAIL ELEVATOR ARE NOT LABELED. ART. 110.22
RSLV 07/09/2018 07/09/2018 07/23/2018
 
007 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(BASEMENT) ELEVATOR E PIPE NOT SUPPORTED ABOVE DISCO. ART. 358.30
RSLV 07/09/2018 07/09/2018 07/23/2018
 
008 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(CELLAR)ALL PIT RECEPTACLES FOR OIL MIX PUMP HAS NOT BEEN INSTALLED. ART.110.2
RSLV 07/09/2018 07/09/2018 07/23/2018
 
009 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
(CELLAR) ELEVATOR G PIT HAS DEFECTIVE GFCI. ART. 620.85
RSLV 07/09/2018 07/09/2018 07/23/2018
 
010 (231) NO OTHER OUTLET
(CELLAR) ELEVATOR G RECEPTACLE FOR PUMP NOT SINGLE.
RSLV 07/09/2018 07/09/2018 07/23/2018
 
011 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(ROOF)CKT BREAKER PANEL IN ELEVATOR ROOM FUSED AT 125 AMP ON #3 AWG. ART.240.3
RSLV 07/09/2018 07/09/2018 07/23/2018
 
012 ( 16) DEFECTIVE LIGHTING FIXTURES ARE IN USE
(ROOF) RETAIL ELEVATOR #1 LIGHTS NOT WORKING. ART. 110.2
RSLV 07/09/2018 07/09/2018 07/23/2018
 
013 (308) CONDUCTORS ARE NOT PROPERLY INSTALLED/TERMINATED
(ROOF) DOUBLE LUGGING ON MOTOR ENCLOSURE ON ROOF. ART. 110.14
RSLV 07/09/2018 07/09/2018 07/23/2018
 
014 (320) NO GUARDS FOR LAMPHOLDERS
(ROOF)ELEVATOR A TOP OF CAR HAS NO GUARD FOR LIGHTING FIXTURE. ART. 620.4
RSLV 07/09/2018 07/09/2018 07/23/2018
 
015 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
(ROOF) KO'S ON 1900 BOXES IN MOTOR ROOM. ART. 110.12(A)
RSLV 07/09/2018 07/09/2018 07/23/2018