Electrical Application Details for App #: B414046
Premises: 430 ALBEE SQUARE BROOKLYN BIN: 3425729     Block: 146   Lot: 51
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 436 ALBEE SQUARE Census Tract:   15
CEL,6,9,12,15,18,21,24,27,ROOF Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11201 Community Board:   302
Related Job Number:    320917665
DOB Cross Street(s):   GOLD STREET,    FULTON STREET
Status:   C - JOB IS SIGNED OFF 03/10/2018
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   07/08/2016 Job Start Date:   07/14/2016
Last Change:   03/10/2018 Job End Date:   07/06/2018
Appointment Status:   
Last Inspection By:   SCHUSZTER, NORBET       On     03/08/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012311 Licensee Name: MOSES ROSENBERGER
Firm: 004090 Firm Name: HIVOLTS ELECTRICAL INC
Firm Phone: 718-855-4346  Firm Address: 21 HERKIMER PLACE BROOKLYN NY 11216 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $5,040.00
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (4  Stores, 144 Apartments)
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   53924     Submittal #: 16A0301  
Owner / Occup:
Owner Business Name: ALBEE SQUARE LLC
Authorized Representative:  YOEL GOLDMAN
Relationship To Owner:   PARTNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  2  FA
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  2  600A
D. 601 Up to 1200 AMPS  3  1200A
E. Over 1200 AMPS  2  2000A 2500A
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  
B. Over #2 to 1/0  12  
C. Over 1/0 to 250 MCM  13  
D. Over 250 MCM  37  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  
D. 3 Phase Over 225 AMPS  1  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL          11    125         
006          22               
009          18               
012          18               
015          18               
018          18               
021          18               
024          18               
027          18               
ROF            200  100     
Buildings Total       167       325     100      
Total Units : 592 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 148 #4-Wire 0 #10-Wire 2
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/08/2016 Notice: 1 - FIRST NOTICE 02/22/2018
Power Issued: 07/08/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  THIS PERMIT IS IN CONJUCTION WITH ADVISORY BOARD FILING ONLY

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B414046
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/11/2018 02/12/2018 CLC V (180) (3)
INSPECTION COMMENTS: INSPECTION FAIL, PRIOR TO INSPECTION WATER LEAKING FROM CONED WIRES, CHECK PROPERTY LINE BOX FOR BONDING, PRIOR TO INSPECTION ALL SHED ARE REMOVED
 
(2) 02/21/2018 02/22/2018 EID V R (80) (1)
INSPECTION COMMENTS: OBJ. REMOVED. NEW ISSUED.
 
(3) 03/08/2018 03/08/2018 NRS C R (71) (0)
INSPECTION COMMENTS: OBJECTION REMOVED.

OBJECTION FOR APPLICATION #: B414046
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 19) DEFECTIVE WIRING IS IN USE
(BASEMENT) WATER LEAKING ON THE SERVICE ENTRANCE BUS 110.12 B
RSLV 02/11/2018 02/11/2018 02/21/2018
 
002 (999) OTHER
(ROOF)FIRE ALARM TAP ON LOAD SIDE OF GENERATOR DISCONNECT NYC AMEND 700.10E 1
RSLV 02/11/2018 02/11/2018 02/21/2018
 
003 (999) OTHER
(ROOF) GENERATOR NEUTRAL BONDED 250.24 A 5
RSLV 02/11/2018 02/11/2018 02/21/2018
 
004 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(ROOF) NO GEC OR SUPP. GND CONDUCTOR PROVIDED FOR GENERATOR.
RSLV 02/21/2018 02/21/2018 03/08/2018