| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
1 |
|
| B. 101 Up to 200 AMPS |
1 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
1 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
1 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
1 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
INSP ID |
FIELD DATE |
DISP DATE |
INSP ID |
FLD DISP |
OBJ DISP |
ENRG REC |
TIME INSP |
REINSP DATE |
NEW OBJ |
APPT FLAG |
| |
| (1) |
03/08/2023 |
03/08/2023 |
DIT |
J |
|
|
(34) |
|
(0) |
Y |
| INSPECTION COMMENTS:
|
JOB IN PROGRESS , FULL INSPECTION REQUIRED
|
| |
| (2) |
04/05/2023 |
04/05/2023 |
KVF |
V |
|
|
(20) |
|
(6) |
|
| INSPECTION COMMENTS:
|
INSPECTION COMPLETE, SELF CERT OBJECTIONS ISSUED
|
| |
| (3) |
04/18/2023 |
04/18/2023 |
PP1 |
J |
Y |
|
(0) |
|
(0) |
|
| INSPECTION COMMENTS:
|
CERTIFIED - OBJ-23-000015975
|
| |
| (4) |
04/18/2023 |
04/18/2023 |
PP1 |
J |
Y |
|
(0) |
|
(0) |
|
| INSPECTION COMMENTS:
|
CERTIFIED - OBJ-23-000015978
|
| |
| (5) |
04/18/2023 |
04/18/2023 |
PP1 |
J |
Y |
|
(0) |
|
(0) |
|
| INSPECTION COMMENTS:
|
CERTIFIED - OBJ-23-000015979
|
| |
| (6) |
04/18/2023 |
04/18/2023 |
PP1 |
J |
Y |
|
(0) |
|
(0) |
|
| INSPECTION COMMENTS:
|
CERTIFIED - OBJ-23-000015980
|
| |
| (7) |
04/18/2023 |
04/18/2023 |
PP1 |
J |
Y |
|
(0) |
|
(0) |
|
| INSPECTION COMMENTS:
|
CERTIFIED - OBJ-23-000015981
|
| |
| (8) |
04/24/2023 |
04/24/2023 |
EID |
C |
R |
|
(0) |
|
(0) |
|
| INSPECTION COMMENTS:
|
CERTIFIED - OBJ-23-000016728
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (FLOOR: 001) ART 422.30-35 MICROWAVE DISCO SWITCH IS NOT AS PER CODE |
RSLV |
04/05/2023 |
04/05/2023 |
04/18/2023 |
| |
| 002 |
( 30) |
OUTLET BOXES ARE NOT SECURED (FLOOR: 001) ART.314.23 COUNTER TOP GFCI ON 1ST FLOOR NOT SECURED |
RSLV |
04/05/2023 |
04/05/2023 |
04/18/2023 |
| |
| 003 |
(125) |
PROTECTION OF CONDUCTORS NOT INSTALLED AS PER CODE (ALL FLOORS)ART 410.40-46 ALL WALL MOUNT LIGHT ARE NOT PROPERLY BONDED |
RSLV |
04/05/2023 |
04/05/2023 |
04/24/2023 |
| |
| 004 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (ALL FLOORS)ART.314.20 SLEEVES REQUIRED FOR ALL LIGHT SWITCHES AND OUTLETRECEPTACLES |
RSLV |
04/05/2023 |
04/05/2023 |
04/18/2023 |
| |
| 005 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (BASEMENT)ART250.148 LIGHT SWITCH NEAR JACUZZI AREA MISSING EGC BOND |
RSLV |
04/05/2023 |
04/05/2023 |
04/18/2023 |
| |
| 006 |
( 29) |
OUTLET BOXES ARE NOT COVERED (BASEMENT)ART.314.25 LIGHT SWITCH NEAR SHOWER IN BASEMENT IS NOT COVERED ASPER CODE |
RSLV |
04/05/2023 |
04/05/2023 |
04/18/2023 |