Electrical Application Details for App #: B413939
Premises: 546 48 STREET BROOKLYN BIN: 3012653     Block: 775   Lot: 25
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 546 48TH ST Census Tract:   98 Health Area:  6500
48YH STREET Admin Area:   B - BROOKLYN Inspection Area:   J
BROOKLYN, NY 11220 Community Board:   307
DOB Cross Street(s):    5 AVENUE,    6 AVENUE
Status:   C - JOB IS SIGNED OFF 12/23/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/06/2016 8:53 PM
Application Entered:   07/06/2016 Job Start Date:   07/06/2016
Last Change:   12/23/2016 Job End Date:   09/01/2016
Appointment Status:   
Last Inspection By:   JEFFERSON, CHARLES       On     12/01/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012818 Licensee Name: JASON P SAMPOGNA
Firm: 004672 Firm Name: TAURUS ELEC'L CONT'G INC
Firm Phone: 718-207-7765  Firm Address: 200 6TH STREET, SUITE 3G BROOKLYN NY 11215 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
S - SUSTAINABLE ENERGY - GENERAL
Total Fee:  $55.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   B - Two Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ANDREW SCHERER
Owner Business Name: NA
Authorized Representative:  JASON SAMPOGNA
Relationship To Owner:   MASTER ELECTRICIAN


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  1 SET #10 FEEDERS
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                     
ROF              15         
Buildings Total                     
Total Units : 9 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 11/10/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  ELECTRICAL PERMIT FOR 15 LG 315 WATT MODULES, S.B 5.0 INVERTER, #10 FEEDERS TO 2POLE 30A BREAKER - MSP: 200A MAIN BREAKER, 200A PANEL RATING

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B413939
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/13/2016 10/13/2016 CLC V (45) (1)
INSPECTION COMMENTS: INSPECTION FAIL
 
(2) 11/10/2016 11/10/2016 EBA V R (35) (1)
INSPECTION COMMENTS: FAIL
 
(3) 12/01/2016 12/01/2016 CJE C R (25) (0)
INSPECTION COMMENTS: OBJECTION REMOVED

OBJECTION FOR APPLICATION #: B413939
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(BASEMENT)LIQUIDTIGHT NOT APPROVED FOR DIRECT BURIAL 350.10 (3) BASEMENTPENETRAION OUTSIDE
RSLV 10/13/2016 10/13/2016 11/10/2016
 
002 (999) OTHER
(BASEMENT)NO CONTINIUTY, NO CHANGE OVER USED BETWEEN SEALTIGHT AND CONDUIT110.2 / 250.64.C.
RSLV 11/10/2016 11/10/2016 12/01/2016