BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B413913
Premises: 117 LIVINGSTON STREET BROOKLYN BIN: 3425971     Block: 154   Lot: 40
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 415 RED HOOK LANE Census Tract:   37 Health Area:  2400
CELLAR, FLOORS 1 - 21, ROOF Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11201 Community Board:   302
Related Job Number:    320626747
DOB Cross Street(s):       BOERUM PLACE
Status:   C - JOB IS SIGNED OFF 09/28/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/06/2016 1:12 PM
Application Entered:   07/06/2016 Job Start Date:   07/08/2016
Last Change:   09/28/2018 Job End Date:   07/01/2019
Appointment Status:   
Last Inspection By:   SEVERIANO JOHN       On     01/23/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012245 Licensee Name: PETER ARANA
Firm: 003988 Firm Name: SANT-TEC ELECTRIC INC
Firm Phone: 718-644-7645  Firm Address: 516 INDUSTRIAL LOOP 2ND FL STATEN ISLAND NY 10309 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
L - LIGHTING WORK
Total Fee:  $5,040.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  320626747
Building Used As:   Z - Commercial/Residential (2  Stores, 108 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: TIMOTHY QUINLAN
Owner Business Name: RED HOOK LANE LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  92  90- #2, 2-#6
B. Over #2 to 1/0  22  22-#1
C. Over 1/0 to 250 MCM  1  3/0
D. Over 250 MCM  16  2-350, 14-500
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  108  100 AMP
C. 3 Phase Up to 225 AMPS  7  4 - 100 A, 3 - 225 A
D. 3 Phase Over 225 AMPS  4  1-400A, 1-800A, 2-1200A
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  2  20 HP
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    54  24    15  54  14  100         
001    39    20  79             
002    36    10  36             
003    36  97    26  58             
004    10  171    51  49             
005    11  171    51  51             
006    12  190    50  55             
007    12  190    50  55             
008    12  190    50  55             
009    12  190    50  55             
010    12  190    50  55             
011    12  190    50  55             
012    12  190    50  55             
013    12  190    50  55             
014    12  190    50  55             
015    11  127    33  42             
016    11  127    33  42             
017    11  127    33  42             
018    11  127    33  42             
019    11  127    33  42             
020    11  127    33  42             
021    11  127    33  42             
ROF    25    12  25  11  100  22     
Buildings Total 396  3077    866  1141     200     22      
Total Units : 5702 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 12/12/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B413913
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/12/2017 12/12/2017 EID V (218) (5)
INSPECTION COMMENTS: INSPECTION COMPLETED. OBJ. ISSUED
 
(2) 12/21/2017 12/23/2017 JKJ J Y (20) (0)
INSPECTION COMMENTS: 1 OBJECTION STILL REMAINS NO GROUND TO TRANSFORMER ELEVATOR
 
(3) 01/23/2018 01/23/2018 SVJ C R (1) (0)
INSPECTION COMMENTS: SEE B408844, FILED FOR ELEVATORS

OBJECTION FOR APPLICATION #: B413913
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
(ROOF) BULKHEAD: NO GND PROVIDED TO GENERATOR
RSLV 12/12/2017 12/12/2017 12/21/2017
 
002 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
(ROOF)BULKHEAD: PANELS T-OUT: SHEETMETAL SCREWS USED FOR MOUNTING GND BARS
RSLV 12/12/2017 12/12/2017 12/21/2017
 
003 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
(ROOF) ELEVATOR MTR. RM: NO GND PROVIDED FOR TRANSFORMERS
RSLV 12/12/2017 12/12/2017 01/23/2018
 
004 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(ROOF) BULKHEAD: HPPBR: #2 CONDUCTOR FEEDING SUB-PANEL FUSED AT 200A
RSLV 12/12/2017 12/12/2017 12/21/2017
 
005 ( 29) OUTLET BOXES ARE NOT COVERED
(ROOF)UNFINISHED/OPEN BOXES AT GENERATOR AND OPEN LBS AT COOLING TOWER.
RSLV 12/12/2017 12/12/2017 12/21/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.