BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B413525
Premises: 1834 FULTON STREET BROOKLYN BIN: 3347027     Block: 1703   Lot: 14
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 835 HERKIMER ST Census Tract:   299 Health Area:  3600
001,CEL Admin Area:   B - BROOKLYN Inspection Area:   E
BROOKLYN, NY 11233 Community Board:   303
DOB Cross Street(s):   SUYDAM PLACE,    BUFFALO AVENUE
Status:   C - JOB IS SIGNED OFF 11/08/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/27/2016 3:26 PM
Application Entered:   06/27/2016 Job Start Date:   06/27/2016
Last Change:   11/08/2018 Job End Date:   06/01/2017
Appointment Status:   
Last Inspection By:   NAJI PHILLIIPS       On     10/15/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012188 Licensee Name: ARYEH YARMARK
Firm: 004184 Firm Name: NET POWER ELECTRIC CORP
Firm Phone: 718-837-8800  Firm Address: 1202 AVE J 3RD FLOOR BROOKLYN NY 11210 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $225.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   I - Hospital Or Health Facility
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ROBERT J DEVITO
Owner Business Name: BROOKLYN GARDENS NURSING
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  1  ONE SET 1/0 4 WIRE
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  100 AMP PANEL 3PH
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    120  150    40  120             
Buildings Total 120  150    40  120                
Total Units : 430 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 10/11/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B413525
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/05/2018 10/05/2018 JGX J (27) (0) Y
INSPECTION COMMENTS: CONTRACTOR STATED HE HAD CALLED THE OFFICE ON THURS 10/04/2018 TO CANCEL INSPECTION.
 
(2) 10/11/2018 10/11/2018 JGX V (51) (2)
INSPECTION COMMENTS: INSPECTION OF APP B413525 ONLY IS COMPLETED. 2 # OBJECTIONS ISSUED.
 
(3) 10/15/2018 10/15/2018 NJP C R (20) (0)
INSPECTION COMMENTS: THE JOB IS OK.

OBJECTION FOR APPLICATION #: B413525
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (123) SERVICE DISCONNECTS ARE NOT PROPERLY GROUPED/LABELED
(CELLAR)DISTRUBUTION SWITCHGEAR NOT PROPERLY IDENTIFIED. ART. 230.72 A
RSLV 10/11/2018 10/11/2018 10/15/2018
 
002 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(CELLAR) NO DIRECTORY FOR PANEL LTE-WC. ART. 408.4
RSLV 10/11/2018 10/11/2018 10/15/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.