BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B413146
Premises: 495 2 STREET BROOKLYN BIN: 3425110     Block: 1076   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 187 7 AV Census Tract:   155 Health Area:  4500
BASEMENT, 1ST,2ND,3RD,4TH ,5TH Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11215 Community Board:   306
Related Job Number:    321201739
DOB Cross Street(s):    1 STREET,    2 STREET
Status:   C - JOB IS SIGNED OFF 03/17/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/19/2016 11:59 PM
Application Entered:   06/19/2016 Job Start Date:   06/20/2016
Last Change:   03/17/2017 Job End Date:   05/25/2017
Appointment Status:   
Last Inspection By:   ADMINISTRATION       On     03/08/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012768 Licensee Name: SENAD MEHOVIC
Firm: 004614 Firm Name: E & M ELECTRICAL NY CORP
Firm Phone: 718-281-0158  Firm Address: 193-02 NORTHERN BLVD FLUSHING NY 11358 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $737.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (1  Stores, 4 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: PETER SAMKO
Owner Business Name: 187 7 AV RESIDENCES LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  4  
C. Over 1/0 to 250 MCM  1  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  4  
C. 3 Phase Up to 225 AMPS  2  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
EPT                   
BAS    40  14    10               
MZ1    24             
MZ2    42  57    34           
MZ3    42  57    34           
MZ4    42  57    34           
MZ5    42  57    34           
ROF                     
Buildings Total 239  252    150            17      
Total Units : 658 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 4 #4-Wire 2 #10-Wire 0
Existing Meters 12 + New Meters 6 - Removed Meters 12 = Total Meters 6

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/19/2016 Notice: 1 - FIRST NOTICE 02/28/2017
Power Issued: 06/19/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B413146
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/28/2017 02/28/2017 JRP V (90) (8)
INSPECTION COMMENTS: FAIL
 
(2) 03/08/2017 03/09/2017 ADM C R (47) (0)
INSPECTION COMMENTS: CONTRACTOR MADE ALL CORRECTIONS TO PREVIOUS OBJECTIONS.

OBJECTION FOR APPLICATION #: B413146
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS)ALL OVERCURRENT PROTECTION FOR A/C CONDENSERS ON ROOF ARE OVER FUSE240.3
RSLV 02/28/2017 02/28/2017 03/08/2017
 
002 (999) OTHER
(ALL FLOORS) NO EMERGENCY ILLUMINATION IN STAIRWAY 700.16
RSLV 02/28/2017 02/28/2017 03/08/2017
 
003 (999) OTHER
(BASEMENT)MISSING ONE CONDUCTOR IN PARALLEL PHASE ON LOAD SIDE OF MAINSERVICE DISCONNECT 310.4
RSLV 02/28/2017 02/28/2017 03/08/2017
 
004 (999) OTHER
(BASEMENT) MAIN FUSE FOR PLP PANEL OVERSIZE 310.16, 240.3
RSLV 02/28/2017 02/28/2017 03/08/2017
 
005 (999) OTHER
(BASEMENT)FIRE ALARM SWITCH DISCONNECT NOT CONNECTED IN LINE SIDE NYCAMENDMENT 760.41(A)(1)
RSLV 02/28/2017 02/28/2017 03/08/2017
 
006 (999) OTHER
(GROUND FLOOR)UNBALANCE AMPACITY PARALLEL CONDUCTORS IN LOAD SIDE 310.4
RSLV 02/28/2017 02/28/2017 03/08/2017
 
007 (999) OTHER
(GROUND FLOOR) NO SHOW WINDOW RECEPTACLES IN COMMERCIAL STORE 210.62
RSLV 02/28/2017 02/28/2017 03/08/2017
 
008 (999) OTHER
(ROOF) ALL GFCI RECEPTACLES ON ROOF NOR WR 406.8(B)
RSLV 02/28/2017 02/28/2017 03/08/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back