| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
4 |
100 AMP SERVICE SWITCHES |
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
4 |
3 #2 |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
1 |
SET OF #3 3/0 |
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
3 |
SINGLE PH UP TO 20 BREAK |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (FLOOR: 001) 1ST FL APT GFCI MISSING ON RIGHT SIDE OF STOVE 210.52 |
RSLV |
03/09/2017 |
03/09/2017 |
04/14/2017 |
| |
| 002 |
(999) |
OTHER (FLOOR: 001) BACK YARD SEAL TIGHT RAN OVER 6 FT 350.12 3 AMEND |
RSLV |
03/09/2017 |
03/09/2017 |
04/14/2017 |
| |
| 003 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX (FLOOR: 003) 3RD FL APT OK MISSING IN PANEL |
RSLV |
03/09/2017 |
03/09/2017 |
04/14/2017 |
| |
| 004 |
( 45) |
FIXTURE NOT INSTALLED IN AN APPROVED MANNER (ALL FLOORS)THOUGH OUT BATH ROOM FIXTURES NOT APPROVED FOR DAMP LOCATION 410.10A |
RSLV |
03/09/2017 |
03/09/2017 |
04/14/2017 |
| |
| 005 |
(999) |
OTHER (ALL FLOORS)THOUGH OUT KITCHENS UNDER CAB LIGHTS ON WITH COUNTER CIRCUITS 210.52B 2 |
RSLV |
03/09/2017 |
03/09/2017 |
04/14/2017 |
| |
| 006 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER (BASEMENT) ALL SERVICE SWITCHES NEUTRALS NOT BONDED 250.24 B |
RSLV |
03/09/2017 |
03/09/2017 |
04/14/2017 |
| |
| 007 |
(999) |
OTHER (BASEMENT)SERVICE ENTRANCE COND RAN IN THE HOLLOW FRAME OF THE BUILDING 230.43AMEND |
RSLV |
03/09/2017 |
03/09/2017 |
04/14/2017 |
| |
| 008 |
(999) |
OTHER (BASEMENT) COMMUNICATION BAR NOT PROVIDED 250.94 |
RSLV |
03/09/2017 |
03/09/2017 |
04/14/2017 |
| |
| 009 |
(999) |
OTHER (BASEMENT)GROUNDING ELECTRODE CONDUCTORS NOT ON NEUTRAL BARS 250.24 A |
RSLV |
03/09/2017 |
03/09/2017 |
04/14/2017 |