Electrical Application Details for App #: B412979
Premises: 805 ST MARKS AVENUE BROOKLYN BIN: 3341622     Block: 1221   Lot: 53
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 805 SAINT MARKS AV Census Tract:   313 Health Area:  2900
MOBILE BOILER Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11213 Community Board:   308
DOB Cross Street(s):   NEW YORK AVENUE,    BROOKLYN AVENUE
Status:   C - JOB IS SIGNED OFF 07/04/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/15/2016 2:45 PM
Application Entered:   06/15/2016 Job Start Date:   06/16/2016
Last Change:   07/04/2017 Job End Date:   12/16/2016
Appointment Status:   
Last Inspection By:   JOHN, CHARLES       On     06/08/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009791 Licensee Name: JOSEPH B JORDAN
Firm: 004329 Firm Name: GOTHAM WIRING LICENSED
Firm Phone: 718-295-6430  Firm Address: 649A EAST 183RD STREET ELECTRICAL CONTRACTORS IN BRONX NY 10458 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
8 - BOILER/BURNER WIRING
Total Fee:  $52.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: SHLOMIE BROCINER
Owner Business Name: SJ FUEL COMPANY
Authorized Representative:  JOSEPH JORDAN
Relationship To Owner:   CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  1  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 04/28/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B412979
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/15/2017 02/16/2017 CJE V (28) (5)
INSPECTION COMMENTS: CORRECT ALL OBJECTIONS.
 
(2) 04/04/2017 04/06/2017 FDY N (9) (0) Y
INSPECTION COMMENTS: CALLED CONTRACTOR AND THE CONTRACTOR DID NOT SHOW UP. ACCIDENTLY WENT A WRONG ROUTE.
 
(3) 04/26/2017 04/28/2017 FDY V R (45) (1)
INSPECTION COMMENTS: NEW OBJECTION ISSUED.
 
(4) 06/08/2017 06/09/2017 CJH C R (32) (0)
INSPECTION COMMENTS: OBJECTION REMOVED

OBJECTION FOR APPLICATION #: B412979
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(BASEMENT) MULTI WIRE CKT NOT GROUPED. ART. 210.4(D)
RSLV 02/15/2017 02/15/2017 04/26/2017
 
002 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(BASEMENT)MULTI WIRE CKTS MEANS OF DISCONNECT NOT SIMULTANEOUS. ART. 210.4(B)
RSLV 02/15/2017 02/15/2017 04/26/2017
 
003 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
(BASEMENT) GFCI RECEPTACLE DO NOT RESET. AMEND. 110.2(A)
RSLV 02/15/2017 02/15/2017 04/26/2017
 
004 (220) DOUBLE LUGGING IN SERVICE SWITCH
(BASEMENT) E.G.C DOUBLE LUGGED IN PANEL. ART. 110.14(A)
RSLV 02/15/2017 02/15/2017 04/26/2017
 
005 (328) CIRCUIT CONDUCTORS NOT GROUPED
(BASEMENT) CONDUCTORS NOT GROUPED. ART. 300.20
RSLV 02/15/2017 02/15/2017 04/26/2017
 
006 (999) OTHER
(CELLAR) 240.6 14 AWG ON A 20 AMP BREAKER.
RSLV 04/26/2017 04/26/2017 06/08/2017