BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B411425
Premises: 644 10 STREET BROOKLYN BIN: 3026194     Block: 1095   Lot: 12
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 644 10 ST Census Tract:   167 Health Area:  4600
CELLAR Admin Area:   B - BROOKLYN Inspection Area:   F
BROOKLYN, NY 11215 Community Board:   306
DOB Cross Street(s):    8 AVENUE,    PROSPECT PARK WEST
Status:   C - JOB IS SIGNED OFF 07/22/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/12/2016 12:33 PM
Application Entered:   05/12/2016 Job Start Date:   05/12/2016
Last Change:   07/22/2017 Job End Date:   05/12/2017
Appointment Status:   
Last Inspection By:   CAMPBELL, C       On     03/09/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010672 Licensee Name: VITO LIOTINE
Firm: 001703 Firm Name: PRO ELECTRIC CORP.
Firm Phone: 718-625-1995  Firm Address: 68 JAY STREET BROOKLYN NY 11201 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $108.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   B - Two Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: GARY DAVIS
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  100AMP
B. 101 Up to 200 AMPS  1  200AMP
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  3/0
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  1PHASE UP TO 20-1
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 2 #4-Wire 0 #10-Wire 0
Existing Meters 2 + New Meters 2 - Removed Meters 2 = Total Meters 2

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 05/12/2016 Notice: 1 - FIRST NOTICE 06/27/2016
Power Issued: 05/12/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  THIS JOB WAS FILED BY OTHER BUT WAS NOT COMPLETED (HELLER ELECTRIC CO. INC. 620 CONEY ISLAND AVE. BROOKLYN, NY 11219, PERMIT #B326546).

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B411425
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/27/2016 06/27/2016 EBA V (30) (4)
INSPECTION COMMENTS: FAIL
 
(2) 03/09/2017 03/10/2017 CLC C R (45) (0)
INSPECTION COMMENTS: INSPECTION PASS , INSPECT SERVICE WORK ONLY

OBJECTION FOR APPLICATION #: B411425
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(BASEMENT) NO GROUND BAR 250.64
RSLV 06/27/2016 06/27/2016 03/09/2017
 
002 (999) OTHER
(BASEMENT) NO INTERCONNECTION BAR 250.94
RSLV 06/27/2016 06/27/2016 03/09/2017
 
003 (999) OTHER
(BASEMENT) NO GROND ROD 250.53.D.2.
RSLV 06/27/2016 06/27/2016 03/09/2017
 
004 (999) OTHER
(BASEMENT) NO WATERMETER JUMPER 250.53.D.1.
RSLV 06/27/2016 06/27/2016 03/09/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order