BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B411042
Premises: 42 3 PLACE BROOKLYN BIN: 3005350     Block: 370   Lot: 25
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 42 3RD PL Census Tract:   65 Health Area:  4100
1FL THROUGH 4TH FL Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11231 Community Board:   306
Related Job Number:    310045019
DOB Cross Street(s):   HENRY STREET,    CLINTON STREET
Status:   C - JOB IS SIGNED OFF 08/29/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/04/2016 9:27 AM
Application Entered:   05/04/2016 Job Start Date:   05/05/2016
Last Change:   08/29/2016 Job End Date:   03/30/2017
Appointment Status:   
Last Inspection By:   BANYA, E       On     08/27/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011769 Licensee Name: ZHENG LI
Firm: 003451 Firm Name: KJK ELECTRIC INC
Firm Phone: 917-682-3886  Firm Address: 79 BRIDGEWATER STREET BROOKLYN NY 11222 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $224.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   B - Two Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MAGGIE CHAN
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  2  3/0 AWG WIRE
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  2  30 CK MAIN LUG PANEL
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    30  20    15  30         
002    30  20    14  30         
003    30  20    12  30         
004    30  20    12  30         
Buildings Total 120  80    53  120     16           
Total Units : 389 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 07/27/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B411042
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/23/2016 07/27/2016 DAH V (15) (5)
INSPECTION COMMENTS: THE JOB IS NOT GOOD
 
(2) 08/27/2016 08/29/2016 EBA C R (30) (0)
INSPECTION COMMENTS: VIOLATIONS REMOVED

OBJECTION FOR APPLICATION #: B411042
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 001) WALL SWITCHES NOT AS PER ARTL.110.2
RSLV 07/23/2016 07/23/2016 08/27/2016
 
002 ( 19) DEFECTIVE WIRING IS IN USE
(ROOF) DS ARE NOT PROPERLY SUPPORTED
RSLV 07/23/2016 07/23/2016 08/27/2016
 
003 ( 53) GFCI HAS NOT BEEN PROVIDED
(ROOF) WITHIN 25' OF AC UNITS
RSLV 07/23/2016 07/23/2016 08/27/2016
 
004 (999) OTHER
(ROOF) NEUTRAL IN DS ARTL.250.24(A)(5)
RSLV 07/23/2016 07/23/2016 08/27/2016
 
005 (999) OTHER
(ROOF) SEALTIGHT IN EXCESS OF 6 FT ARTL.350.60
RSLV 07/23/2016 07/23/2016 08/27/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.