BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B409921
Premises: 50 PLAZA STREET EAST BROOKLYN BIN: 3029312     Block: 1170   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 50 PLAZA ST E Census Tract:   207 Health Area:  4500
5C Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11238 Community Board:   308
DOB Cross Street(s):   VANDERBILT AVENUE,    BUTLER PLACE
Status:   C - JOB IS SIGNED OFF 02/03/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/10/2016 9:34 PM
Application Entered:   04/10/2016 Job Start Date:   04/11/2016
Last Change:   02/03/2017 Job End Date:   04/11/2018
Appointment Status:   
Last Inspection By:   DAMISO COOTE       On     01/31/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012291 Licensee Name: MIROSLAW K PARYS
Firm: 004056 Firm Name: TOP TEAM ELECTRIC LLC
Firm Phone: 212-683-4142  Firm Address: 234 FIFTH AVENUE, SUITE 4322 NEW YORK NY 10001 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $55.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MARLENY RAFFERTY
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
005  5C  30  22  13             
Buildings Total 30  22  13                
Total Units : 73 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 12/16/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B409921
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/12/2016 10/13/2016 DNM N (15) (0) Y
INSPECTION COMMENTS: ELECTRICIAN DID NOT SHOW.
 
(2) 10/28/2016 10/31/2016 CLC V (45) (4)
INSPECTION COMMENTS: INSPECTION FAIL CORRECT ALL OBJECTION
 
(3) 12/15/2016 12/16/2016 CJH V Y (34) (2)
INSPECTION COMMENTS: OBJECTION PARTIALLY REMOVED
 
(4) 01/31/2017 01/31/2017 DIT C R (43) (0)
INSPECTION COMMENTS: OBJECTIONS RESOLVED

OBJECTION FOR APPLICATION #: B409921
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(FLOOR: 005) APT 5C PANEL MISSING KO
RSLV 10/28/2016 10/28/2016 12/15/2016
 
002 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 005) APT 5C KITCHEN ISLAND GFCI 'S NOT PROVIDED 210.52
RSLV 10/28/2016 10/28/2016 12/15/2016
 
003 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(FLOOR: 005) APT 5C SMALL BEDRM AC NOT AFCI 210.12
RSLV 10/28/2016 10/28/2016 01/31/2017
 
004 (999) OTHER
(FLOOR: 005) APT 5C KITCHEN OUTLETS NOT TR 406.11
RSLV 10/28/2016 10/28/2016 12/15/2016
 
005 (312) AC OUTLET NOT PROVIDED
(FLOOR: 005) APT 5C AC RECEPT OUTLET NOT INSTALLED 210.52 (I) AMEN
RSLV 12/15/2016 12/15/2016 01/31/2017
 
006 (999) OTHER
(FLOOR: 005) APT 5C PNL CKT NOT GROUPED 210.4 D
RSLV 12/15/2016 12/15/2016 01/31/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.