| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
1 |
400 AMPS |
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
2 |
3/0 THHN |
| D. Over 250 MCM |
1 |
500 MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
2 |
42 CIRCUITS |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(128) |
NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH (FLOOR: 001) 001 FL PNL NEU 250.24 A5 |
OPEN |
10/05/2016 |
10/05/2016 |
|
| |
| 002 |
(999) |
OTHER (FLOOR: 001) 001 FL PNL MULTI CKT NEED TWO POLE BRAKERS 210.4B |
OPEN |
10/05/2016 |
10/05/2016 |
|
| |
| 003 |
(220) |
DOUBLE LUGGING IN SERVICE SWITCH (CELLAR) CELLAR SVC CONDUCTOR 110.14 |
OPEN |
10/05/2016 |
10/05/2016 |
|
| |
| 004 |
(279) |
WATER METER JUMPER IS MISSING/IMPROPER (CELLAR) CELLAR SVC SWITCH WATER METER JUMPER 250.53 |
OPEN |
10/05/2016 |
10/05/2016 |
|
| |
| 005 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (CELLAR) ALL PNL NOT LABEL 408.4 |
OPEN |
10/05/2016 |
10/05/2016 |
|
| |
| 006 |
(999) |
OTHER (CELLAR) SVC SWITCH GROUNDING & BONDING UNDER SIZE 250.66 |
OPEN |
10/05/2016 |
10/05/2016 |
|
| |
| 007 |
(999) |
OTHER (CELLAR) SVC SWITCH & DIS SWITCHES GND NOT IDENTIFY 250.119 |
OPEN |
10/05/2016 |
10/05/2016 |
|
| |
| 008 |
(999) |
OTHER (CELLAR) CELLAR 1ST FL PNL CKT NOT GROUPED 210.4D |
OPEN |
10/05/2016 |
10/05/2016 |
|
| |
| 009 |
(999) |
OTHER (CELLAR) CELLAR OLD WIRES & CONDUIT NOT REMOVED 110.2 |
OPEN |
10/05/2016 |
10/05/2016 |
|
| |
| 010 |
( 10) |
BRANCH CIRCUIT CONDUCTORS ARE NOT PROPER SIZE (OPEN SPACE) OUTSIDE UNITS CONDUCTOR NOT SIZE PER UNIT 210.19 |
OPEN |
10/05/2016 |
10/05/2016 |
|
| |
| 011 |
(222) |
USING NON METALLIC SEALTITE NOT APPROVED (OPEN SPACE) OUTSIDE SEAL TIGHT NOT APPROVED 356.10 |
OPEN |
10/05/2016 |
10/05/2016 |
|
| |
| 012 |
(228) |
USING PANEL AS A RACEWAY (OPEN SPACE) OUTSIDE AC DIS SWITCH USED AS RACEWAY 312.8 |
OPEN |
10/05/2016 |
10/05/2016 |
|
| |
| 013 |
(307) |
NO RECEPTACLE OUTLET WITHIN 25 FEET FOR HVAC EQUIPMENT (OPEN SPACE) OUTSIDE AC UNITS RECEPT NOT PROVIDED 210.63 |
OPEN |
10/05/2016 |
10/05/2016 |
|
| |
| 014 |
(999) |
OTHER (OPEN SPACE) OUTSIDE AC UNITS DIS SWITCH FED TWO UNITS 110.2 |
OPEN |
10/05/2016 |
10/05/2016 |
|