BIS Menu  |  Certs. Occupancy  |  After Hours Variance Permit Data  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B409287
Premises: 762 PARK PLACE BROOKLYN BIN: 3330682     Block: 1240   Lot: 12
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 762 PARK PL Census Tract:   317.01 Health Area:  2900
CELLAR THRU 7TH FLOORS Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11216 Community Board:   308
DOB Cross Street(s):   ROGERS AVENUE,    NOSTRAND AVENUE
Status:   C - JOB IS SIGNED OFF 08/21/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/28/2016 12:05 PM
Application Entered:   03/28/2016 Job Start Date:   04/01/2016
Last Change:   08/21/2018 Job End Date:   04/01/2018
Appointment Status:   
Last Inspection By:   NAJI PHILLIIPS       On     06/14/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011193 Licensee Name: ALBERT N FAELLA
Firm: 000907 Firm Name: M F ELEC'L SVC CO., INC
Firm Phone: 718-547-2400  Firm Address: 3323 MERRITT AVENUE BRONX NY 10475 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $3,684.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: BARRETT DEGIGN LLC
Authorized Representative:  AARON HOCKETT
Relationship To Owner:   OWNER REP


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  2  400 AMPS
D. 601 Up to 1200 AMPS  1  1200 AMPS
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  23  3/0 RISERS
D. Over 250 MCM  4  500 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  23  
D. 3 Phase Over 225 AMPS  2  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    19  20  10  19             
001    81  16  81             
002    70  149  50  70             
003    70  149  50  70             
004    70  149  50  70             
005    70  149  50  70             
006    70  149  50  70             
007    67  110  33  67             
ROF    21  17    21             
Buildings Total 538  908  25  299  538                
Total Units : 2308 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 23 #4-Wire 0 #10-Wire 2
Existing Meters 0 + New Meters 25 - Removed Meters 0 = Total Meters 25

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/28/2016 Notice: 1 - FIRST NOTICE 04/23/2018
Power Issued: 03/28/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  GENERAL WIRING OF 23 APARTMENTS NEW SERVICE.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B409287
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/06/2018 03/07/2018 CZH V (137) (3)
INSPECTION COMMENTS: FAIL, SEE OBJECTIONS.
 
(2) 04/23/2018 04/23/2018 DIT V Y (67) (5)
INSPECTION COMMENTS: CORRECT OBJECTIONS
 
(3) 06/14/2018 06/15/2018 NJP C R (40) (0)
INSPECTION COMMENTS: OBJECTIONS RESOLVED.

OBJECTION FOR APPLICATION #: B409287
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS)KITCHEN ISLAND AND COUNTER RECEPT ARE SET BACK TOO FAR. 314.20
RSLV 03/06/2018 03/06/2018 04/23/2018
 
002 (999) OTHER
(BASEMENT) WATER MAIN GROUND NOT ON STREET SIDE. 250.52
RSLV 03/06/2018 03/06/2018 06/14/2018
 
003 (999) OTHER
(BASEMENT)ALL MECHANICAL ROOMS IN B ASEMENT MUST BE GFCI PROTECTED. 210.8
RSLV 03/06/2018 03/06/2018 04/23/2018
 
004 (269) FIRE PUMP SUPPLY CONDUCTORS NOT PROPERLY INSTALLED
(CELLAR) FIRE PUMP CONDUCTORS NOT PROPERLY INSTALLED . ART 695. 6B
RSLV 04/23/2018 04/23/2018 06/14/2018
 
005 (279) WATER METER JUMPER IS MISSING/IMPROPER
(CELLAR) WATER METER JUMPER NOT PROPERLY INSTALLED ART 250.53
RSLV 04/23/2018 04/23/2018 06/14/2018
 
006 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(CELLAR)ALL SERVICE SWITCHES ARE NOT PROPERLY BND TO GEC AND GROUND ROD .ART 250.24 C
RSLV 04/23/2018 04/23/2018 06/14/2018
 
007 (999) OTHER
(CELLAR)FIRE PUMP SERVICE SWITCH NOT PROPERLY BND TO GEC AND GROUND ROD .ART 250.24 C
RSLV 04/23/2018 04/23/2018 06/14/2018
 
008 (999) OTHER
(CELLAR) GEC CANNOT BE TERMINATED ON SPRINKLER MAIN . ART 250
RSLV 04/23/2018 04/23/2018 06/14/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.