| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
2 |
400 AMPS |
| D. 601 Up to 1200 AMPS |
1 |
1200 AMPS |
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
23 |
3/0 RISERS |
| D. Over 250 MCM |
4 |
500 MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
23 |
|
| D. 3 Phase Over 225 AMPS |
2 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER (ALL FLOORS)KITCHEN ISLAND AND COUNTER RECEPT ARE SET BACK TOO FAR. 314.20 |
RSLV |
03/06/2018 |
03/06/2018 |
04/23/2018 |
| |
| 002 |
(999) |
OTHER (BASEMENT) WATER MAIN GROUND NOT ON STREET SIDE. 250.52 |
RSLV |
03/06/2018 |
03/06/2018 |
06/14/2018 |
| |
| 003 |
(999) |
OTHER (BASEMENT)ALL MECHANICAL ROOMS IN B ASEMENT MUST BE GFCI PROTECTED. 210.8 |
RSLV |
03/06/2018 |
03/06/2018 |
04/23/2018 |
| |
| 004 |
(269) |
FIRE PUMP SUPPLY CONDUCTORS NOT PROPERLY INSTALLED (CELLAR) FIRE PUMP CONDUCTORS NOT PROPERLY INSTALLED . ART 695. 6B |
RSLV |
04/23/2018 |
04/23/2018 |
06/14/2018 |
| |
| 005 |
(279) |
WATER METER JUMPER IS MISSING/IMPROPER (CELLAR) WATER METER JUMPER NOT PROPERLY INSTALLED ART 250.53 |
RSLV |
04/23/2018 |
04/23/2018 |
06/14/2018 |
| |
| 006 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY (CELLAR)ALL SERVICE SWITCHES ARE NOT PROPERLY BND TO GEC AND GROUND ROD .ART 250.24 C |
RSLV |
04/23/2018 |
04/23/2018 |
06/14/2018 |
| |
| 007 |
(999) |
OTHER (CELLAR)FIRE PUMP SERVICE SWITCH NOT PROPERLY BND TO GEC AND GROUND ROD .ART 250.24 C |
RSLV |
04/23/2018 |
04/23/2018 |
06/14/2018 |
| |
| 008 |
(999) |
OTHER (CELLAR) GEC CANNOT BE TERMINATED ON SPRINKLER MAIN . ART 250 |
RSLV |
04/23/2018 |
04/23/2018 |
06/14/2018 |