BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B409176
Premises: 152 FREEMAN STREET BROOKLYN BIN: 3064031     Block: 2512   Lot: 38
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 152 FREEMAN ST Census Tract:   563 Health Area:  0100
ENTIRE Admin Area:   B - BROOKLYN Inspection Area:   A
BROOKLYN, NY 11222 Community Board:   301
DOB Cross Street(s):   FRANKLIN STREET,    MANHATTAN AVENUE
Status:   C - JOB IS SIGNED OFF 05/18/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/24/2016 11:17 AM
Application Entered:   03/24/2016 Job Start Date:   03/24/2016
Last Change:   05/18/2017 Job End Date:   03/24/2017
Appointment Status:   
Last Inspection By:   BANYA, E       On     05/01/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010190 Licensee Name: ABE HIMELFARB
Firm: 002663 Firm Name: ALEF ELEC'L CONTR'G INC
Firm Phone: 212-764-2200  Firm Address: 247 WEST 38TH STREET NEW YORK NY 10018 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $429.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: GABI MORITZ
Owner Business Name: HAUS ENTERPRISE LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  5  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  5  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                 
001    12  30  13  12             
002    12  30  13  12             
003    14  34  15  14             
004  4L  11  18  11             
004  4R  11  18  11             
ROF               
Buildings Total 69  142  60  69                
Total Units : 346 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 5 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/24/2016 Notice: 1 - FIRST NOTICE 03/06/2017
Power Issued: 03/24/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INST 15 SD. ONE SPLIT A/C UNIT WITH FIVE BLOWERS

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B409176
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/30/2017 01/31/2017 CCH V (90) (8)
INSPECTION COMMENTS: NOTE NEED TO RE FILE NO-METERS INSTALLED, NO- A/C UNITS NO SERVICE FEEDERS NO- FIRE/ ALARM
 
(2) 03/03/2017 03/06/2017 ADM V R (30) (1)
INSPECTION COMMENTS: FAIL. LOAD LETTER NEEDED
 
(3) 05/01/2017 05/03/2017 EBA C R (40) (0)
INSPECTION COMMENTS: VIOLATION REMOVED

OBJECTION FOR APPLICATION #: B409176
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 001) PANEL IN CLOSET 240.24 D
RSLV 01/30/2017 01/30/2017 03/03/2017
 
002 (999) OTHER
(FLOOR: 002) KITCHEN NOT COMPLETED 210.52 C 2
RSLV 01/30/2017 01/30/2017 03/03/2017
 
003 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 003) PENINSULAR
RSLV 01/30/2017 01/30/2017 03/03/2017
 
004 (999) OTHER
(FLOOR: 003) STOVE OUTLETS NOT 4 PIN FLOOR 2,3.+ 4
RSLV 01/30/2017 01/30/2017 03/03/2017
 
005 (999) OTHER
(FLOOR: 003) 3+4 FLOOR C/T STOVE OUTLET NOT ACCESSIBLE 314.29
RSLV 01/30/2017 01/30/2017 03/03/2017
 
006 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(BASEMENT) M I G B NO WIRE
RSLV 01/30/2017 01/30/2017 03/03/2017
 
007 ( 6) FEEDER DIAGRAM DID NOT ACCOMPANY APPLICATION FOR INSPECTION
(BASEMENT) NO UTILITY BAR
RSLV 01/30/2017 01/30/2017 03/03/2017
 
008 (999) OTHER
(BASEMENT) DRYER NOT 4 PINS 250.142
RSLV 01/30/2017 01/30/2017 03/03/2017
 
009 (999) OTHER
(BASEMENT)BAS, 1 THRU 5. LOAD LETTER NEEDED. 400 AMP SERVICE WITH 5 100PANELS.
RSLV 03/03/2017 03/03/2017 05/01/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.