Electrical Application Details for App #: B409029
Premises: 416 PACIFIC STREET BROOKLYN BIN: 3001135     Block: 190   Lot: 16
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 416 PACIFIC ST Census Tract:   41 Health Area:  2400
B-1-2-3 Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11217 Community Board:   302
DOB Cross Street(s):   BOND STREET,    NEVINS STREET
Status:   C - JOB IS SIGNED OFF 02/28/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/22/2016 8:27 AM
Application Entered:   03/22/2016 Job Start Date:   03/22/2016
Last Change:   02/28/2017 Job End Date:   12/15/2016
Appointment Status:   
Last Inspection By:   ADMINISTRATION       On     02/28/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010523 Licensee Name: VINCENT VERDEROSA
Firm: 001698 Firm Name: SUPER CHARGED ELEC. INC.
Firm Phone: 718-981-7173  Firm Address: 2 DUBOIS AVENUE STATEN ISLAND NY 10310 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $91.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   B - Two Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: M MORRIS
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND    29  22    11  29         
001    31  16    12  31         
002             
003                   
Buildings Total 70  43    28  70              
Total Units : 214 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 01/20/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  GENERAL WIRING , HAVC

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B409029
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/20/2017 01/20/2017 CJH V (56) (5)
INSPECTION COMMENTS: FAIL
 
(2) 02/28/2017 02/28/2017 ADM C R (16) (0)
INSPECTION COMMENTS: OK

OBJECTION FOR APPLICATION #: B409029
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 002) 002 KITCHEN RECEPT OUTLETS NOT GFCI 210.8
RSLV 01/20/2017 01/20/2017 02/28/2017
 
002 (999) OTHER
(GROUND FLOOR) GND FL BATH ROOM GFCI NOT WITHIN 3' OF SINK 210.52 D
RSLV 01/20/2017 01/20/2017 02/28/2017
 
003 (999) OTHER
(GROUND FLOOR) GND FL REAR OUTSIDE LUMINAIRES NOT INSTALLED 110.2
RSLV 01/20/2017 01/20/2017 02/28/2017
 
004 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(ROOF) ROOF AC UNITS OCP NOT PER MFG LISTING 240.3
RSLV 01/20/2017 01/20/2017 02/28/2017
 
005 (999) OTHER
(ROOF) ROOF AC UNITS GFCI NOT INSTALLED 210.63
RSLV 01/20/2017 01/20/2017 02/28/2017