BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B408669
Premises: 8609 BAY 16 STREET BROOKLYN BIN: 3166541     Block: 6367   Lot: 37
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 8609 BAY 16 ST Census Tract:   178
BSMT,GND,2,3,4 Admin Area:   B - BROOKLYN Inspection Area:   N
BROOKLYN, NY 11214 Community Board:   311
DOB Cross Street(s):    86 STREET,    BENSON AVENUE
Status:   C - JOB IS SIGNED OFF 04/27/2016
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   03/15/2016 Job Start Date:   03/08/2016
Last Change:   04/27/2016 Job End Date:   04/30/2016
Appointment Status:   
Last Inspection By:   BANYA, E       On     04/15/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011368 Licensee Name: CHRISTOPHER J STABILE
Firm: 002791 Firm Name: STABILITY ELEC ENTERP INC
Firm Phone: 718-449-8800  Firm Address: 8762 20TH AVENUE BROOKLYN NY 11214-4804 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $1,458.25
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: EVE TONAKIS/VASILANTONAK
Owner Business Name: PERIKLES REALTY, LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  600A, 3-POLE S/S
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  33  #6 THHN FEEDER CONDUCTORS
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  4  #300MCM S/E CONDUCTORS
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  33  32-100A, 1-COMBO
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                 
GND  1-8    16                 
002  9-16    16                 
003  17-24    16                 
004  25-32    16                 
Buildings Total 66  32                
Total Units : 103 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 33 #4-Wire 0 #10-Wire 0
Existing Meters 33 + New Meters 33 - Removed Meters 33 = Total Meters 33

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/15/2016 Notice: 1 - FIRST NOTICE 03/29/2016
Power Issued: 03/15/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  CONTRACTOR #00633 THIS APP IS FILED FOR 1-NEW 208V/600A3-PHASE INDOOR U/G SERVICE AND PARTIAL ADEQUATE WIRING. THISAPP REPLACES B402527

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B408669
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/28/2016 03/29/2016 CJE V (120) (12)
INSPECTION COMMENTS: CORRECT ALL OBJECTION IN ALL APT.
 
(2) 04/15/2016 04/18/2016 EBA C R (60) (0)
INSPECTION COMMENTS: VIOLATIONS REMOVED

OBJECTION FOR APPLICATION #: B408669
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (340) RECEPTACLES NOT TAMPERPROOF
(FLOOR: 001)APT. A-3 RECEPTACLE NEXT TO AC OUTLET NOT TAMPER RESISTANCE. ART.406.11
RSLV 03/28/2016 03/28/2016 04/15/2016
 
002 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(FLOOR: 001)APT. A-3 SINGLE POLE CIRCUIT ON TWO POLE BREAKERS. ART. 110.3(B)
RSLV 03/28/2016 03/28/2016 04/15/2016
 
003 (999) OTHER
(FLOOR: 001)APT. A-3 GAPS AROUND KITCHEN COUNTERTOP RECEPTACLE NOT PROPERLYDONE. PLASTER IS COVERING THE PLATE. ART. 314.21
RSLV 03/28/2016 03/28/2016 04/15/2016
 
004 (999) OTHER
(FLOOR: 001)APT. B-4 MULTI WIRE CIRCUITS MEANS OF DISCONNECT NOT SIMULTANEOUS.ART. 210.4(B)
RSLV 03/28/2016 03/28/2016 04/15/2016
 
005 (999) OTHER
(FLOOR: 001)APT. A-1 MULTI WIRE CIRCUITS MEANS OF DISCONNECT NOT SIMULTANEOUS.ART. 210.4(B)
RSLV 03/28/2016 03/28/2016 04/15/2016
 
006 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS) NO FACE PLATE FOR AC RECEPTACLES. ART. 406.5(B)
RSLV 03/28/2016 03/28/2016 04/15/2016
 
007 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS)DRY WALL SCREWS USED TO MOUNTED PNLS AND OUTLET BOXES. ART 110.3
RSLV 03/28/2016 03/28/2016 04/15/2016
 
008 ( 30) OUTLET BOXES ARE NOT SECURED
(ALL FLOORS)KITCHEN COUNTERTOP OUTLET BOX NOT PROPERLY INSTALLED. ART. 314.23
RSLV 03/28/2016 03/28/2016 04/15/2016
 
009 (999) OTHER
(ALL FLOORS) GAPS AROUND RECEPTACLE PLATES NOT FILLED. ART. 314.21
RSLV 03/28/2016 03/28/2016 04/15/2016
 
010 (999) OTHER
(ALL FLOORS)KITCHEN COUNTERTOP RECEPTACLE OUTLET BOX SET BACK MORE THAN 1/4''ART. 314.20
RSLV 03/28/2016 03/28/2016 04/15/2016
 
011 (243) CONDUCTORS OF THE SAME CIRCUIT NOT GROUPED
(BASEMENT) FEEDER IN PARALLEL NOT GROUPED TOGETHER. ART. 300.3
RSLV 03/28/2016 03/28/2016 04/15/2016
 
012 (244) INDUCED CURRENTS IN METAL ENCLOSURES
(BASEMENT)NO NEUTRAL INSTALLED IN RACEWAY WITH PHASE CONDUCTORS. ART. 300.20
RSLV 03/28/2016 03/28/2016 04/15/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order