BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B408452
Premises: 240 LIVINGSTON STREET BROOKLYN BIN: 3329443     Block: 165   Lot: 22
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 250 LIVINGSTON ST Census Tract:   37 Health Area:  2400
BASEMENT Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11201 Community Board:   302
DOB Cross Street(s):   ELM PLACE,    BOND STREET
Status:   C - JOB IS SIGNED OFF 10/19/2020
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/09/2016 3:48 PM
Application Entered:   03/09/2016 Job Start Date:   03/15/2016
Last Change:   10/19/2020 Job End Date:   06/30/2016
Appointment Status:   
Last Inspection By:   NAJI PHILLIIPS       On     10/07/2020      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012520 Licensee Name: RICHARD E CHIAPPA
Firm: 004443 Firm Name: RC3 ELECTRIC, LLC
Firm Phone: 718-881-8070  Firm Address: 4465 BRONX BLVD BRONX NY 10470 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $210.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (1  Stores, 5 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BERTIE ST. MARTIN
Owner Business Name: VERIZON WIRELESS
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/09/2016 Notice: C - CALL TO OFFICE 09/14/2020
Power Issued: 03/09/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  WE WILL BE INSTALLING A 200 AM 3 PHASE SERVICE FOR VERIZON WIRELESS CELL SITE.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B408452
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/28/2017 08/29/2017 EID N (18) (0) Y
INSPECTION COMMENTS: CONTRACTOR DID NOT SHOW
 
(2) 09/07/2017 09/08/2017 CJE V (49) (2)
INSPECTION COMMENTS: OK
 
(3) 07/29/2020 07/29/2020 SGY N (20) (0) Y
INSPECTION COMMENTS: NO SHOW.
 
(4) 09/14/2020 09/14/2020 SGY V X (30) (3)
INSPECTION COMMENTS: OBJECTION REMAIN. NEW ISSUED.
 
(5) 10/07/2020 10/09/2020 NJP C R (40) (0)
INSPECTION COMMENTS: OBJECTIONS RESOLVED.

OBJECTION FOR APPLICATION #: B408452
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
(BASEMENT) G.C. NOT TERMINATED. ART. 250.4(A)
RSLV 09/07/2017 09/07/2017 10/07/2020
 
002 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(ROOF) EQUIPMENT NOT PROPERLY GROUNDED. ART. 250.112
RSLV 09/07/2017 09/07/2017 10/07/2020
 
003 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(BASEMENT)(ART. 408.4) BASEMENT NOT INSPECTED, SWITCH NOT LABELED, CONTRACTORDOES NOT KNOW LOCATION
RSLV 09/14/2020 09/14/2020 10/07/2020
 
004 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(ROOF) (ART. 250.148) EGC NOT BONDED TO TROFT
RSLV 09/14/2020 09/14/2020 10/07/2020
 
005 ( 27) ARMORED CABLES INSTALLED WITHOUT INSULATING BUSHINGS
(ROOF) (ART. 300.4(G)) BUSHING (TROFT)
RSLV 09/14/2020 09/14/2020 10/07/2020



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order