BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B408386
Premises: 488 12 STREET BROOKLYN BIN: 3026413     Block: 1099   Lot: 20
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 488 12TH ST Census Tract:   167 Health Area:  4600
GROUND Admin Area:   B - BROOKLYN Inspection Area:   F
BROOKLYN, NY 11215 Community Board:   306
DOB Cross Street(s):    8 AVENUE,    PROSPECT PARK WEST
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/08/2016 8:04 PM
Application Entered:   03/08/2016 Job Start Date:   03/09/2016
Last Change:   08/22/2025 Job End Date:   06/09/2016
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   CHARLES COURTNEY       On     11/28/2016      
Field Disp:   J - JOB IN PROGRESS
Energize Recommendation:  
Objection Disposition:  X - NOT REMOVED

License #: 012038 Licensee Name: MONG H LEE
Firm: 003723 Firm Name: KOGEN ELECT'L CONT'G
Firm Phone: 917-775-0155  Firm Address: 52-16 VAN LOON STREET CORP ELMHURST NY 11373 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $63.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   B - Two Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: CHRISTOPHER BUTTERS
Owner Business Name: CHRISTOPHER BUTTERS
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: C - CALL TO OFFICE 11/29/2016
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  GENERAL WIRING

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B408386
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/12/2016 10/13/2016 CCH V (65) (10)
INSPECTION COMMENTS: JOB FAIL NOTE NEED TOTAL INSPECTION
 
(2) 11/28/2016 11/29/2016 CCH J X (55) (0) Y
INSPECTION COMMENTS: NEED TO FILE ALL WORK

OBJECTION FOR APPLICATION #: B408386
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(FLOOR: 001) ALL CIRCUIT
OPEN 10/12/2016 10/12/2016
 
002 (999) OTHER
(FLOOR: 001) 12/3 NOT 2 POLE 210.4B
OPEN 10/12/2016 10/12/2016
 
003 (999) OTHER
(FLOOR: 001) OUTSIDE G F C I NOT W/R 406.8A
OPEN 10/12/2016 10/12/2016
 
004 (999) OTHER
(FLOOR: 001) CIRCUIT NOT GROUP 300.20
OPEN 10/12/2016 10/12/2016
 
005 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(ALL FLOORS) M/C GREEN NOT TO BOX 250.146
OPEN 10/12/2016 10/12/2016
 
006 ( 35) APPROVED OUTLETS HAVE NOT BEEN PROVIDED FOR AIR CONDITIONERS
(ALL FLOORS) THROUGH OUT
OPEN 10/12/2016 10/12/2016
 
007 (999) OTHER
(ALL FLOORS) OUTLETS NOT TAMPER PROOF 406.11
OPEN 10/12/2016 10/12/2016
 
008 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(BASEMENT) NEUTRAL NOT BONDED
OPEN 10/12/2016 10/12/2016
 
009 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(BASEMENT) M I G B MISSING BONDING SCREW
OPEN 10/12/2016 10/12/2016
 
010 (999) OTHER
(BASEMENT) NO UTILITY BAR 250.94
OPEN 10/12/2016 10/12/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.