Electrical Application Details for App #: B408231
Premises: 805 ST MARKS AVENUE BROOKLYN BIN: 3341622     Block: 1221   Lot: 53
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 805 ST MARKS AV Census Tract:   313 Health Area:  2900
ALL FLOORS SERVED, MR Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11213 Community Board:   308
DOB Cross Street(s):   NEW YORK AVENUE,    BROOKLYN AVENUE
Status:   C - JOB IS SIGNED OFF 09/04/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/05/2016 9:02 PM
Application Entered:   03/05/2016 Job Start Date:   03/09/2016
Last Change:   09/04/2018 Job End Date:   03/09/2019
Appointment Status:   
Last Inspection By:   NAJI PHILLIIPS       On     08/31/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011986 Licensee Name: ANTHONY LUCIANO
Firm: 003652 Firm Name: JAM ELECTRICAL CORP
Firm Phone: 212-265-0142  Firm Address: 1133 6TH AVE 28TH FLOOR NEW YORK NY 10036 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $540.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: CALYNNE OYOLOKOR
Owner Business Name: AKELIUS FACILITY MANAGEME
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  4  ELEVATORS
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 08/07/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  MODERNIZATION OF ELEVATOR DEVICE #'S 3P953-3P956 BY ELEVATOR COMPANY IN CONJUNCTION WITH ELEVATOR APPLICATION(273018E).ELEVATOR CONTROL AND LOAD SIDE WIRING ONLY. LCD-68

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B408231
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/12/2018 07/13/2018 NJP V (50) (5)
INSPECTION COMMENTS: CORRECT OBJECTIONS. ELEV CAR A ID#3P953, CAR B ID#3P954 , CAR C ID#3P955 , CAR D ID# 3P956 WAS INSPECTED.
 
(2) 08/06/2018 08/07/2018 NJP V X (30) (1)
INSPECTION COMMENTS: CORRECT OBJECTION. PREVIOUS OBJECTIONS RESOLVED.
 
(3) 08/31/2018 09/04/2018 NJP C R (25) (0)
INSPECTION COMMENTS: OBJECTION RESOLVED. OK TO CLOSE APP. ELEV CAR A ID#3P953, B-ID#3P954 , C-ID#3P955 ,D-ID# 3P956

OBJECTION FOR APPLICATION #: B408231
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(CELLAR) ELEV C OCP OVER FUSED.(ART 240.3)
RSLV 07/12/2018 07/12/2018 08/31/2018
 
002 (315) CONDUCTORS NOT PROPERLY IDENTIFIED
(CELLAR)ELEVATOR A,B,C,D CONDUCTORS NOT PROPERLY INDENTIFIED ON LOAD SIDE OFDISC SWITCH. (ART 200.6/210.5)
RSLV 07/12/2018 07/12/2018 08/31/2018
 
003 (999) OTHER
(CELLAR)DOUBLE LUGGING IN ELEV CAR D CAB LIGHT DISCONNECT .(ART 110.14)
RSLV 07/12/2018 07/12/2018 08/31/2018
 
004 (999) OTHER
(CELLAR)EQUIPMENT GROUND CONDUCTOR LOOSE IN ELEV CAB D DISCONNECT.(ART250.118)
RSLV 07/12/2018 07/12/2018 08/31/2018
 
005 (999) OTHER
(CELLAR) ELEV D FUSE DO NOT MATCH. (ART 240.)
RSLV 07/12/2018 07/12/2018 08/31/2018
 
006 (315) CONDUCTORS NOT PROPERLY IDENTIFIED
(CELLAR) ELEVATOR C CONDUCTORS NOT IDENTIFIED (ART 200.6/210.5)
RSLV 08/06/2018 08/06/2018 08/31/2018