| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
4 |
ELEVATORS |
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE (CELLAR) ELEV C OCP OVER FUSED.(ART 240.3) |
RSLV |
07/12/2018 |
07/12/2018 |
08/31/2018 |
| |
| 002 |
(315) |
CONDUCTORS NOT PROPERLY IDENTIFIED (CELLAR)ELEVATOR A,B,C,D CONDUCTORS NOT PROPERLY INDENTIFIED ON LOAD SIDE OFDISC SWITCH. (ART 200.6/210.5) |
RSLV |
07/12/2018 |
07/12/2018 |
08/31/2018 |
| |
| 003 |
(999) |
OTHER (CELLAR)DOUBLE LUGGING IN ELEV CAR D CAB LIGHT DISCONNECT .(ART 110.14) |
RSLV |
07/12/2018 |
07/12/2018 |
08/31/2018 |
| |
| 004 |
(999) |
OTHER (CELLAR)EQUIPMENT GROUND CONDUCTOR LOOSE IN ELEV CAB D DISCONNECT.(ART250.118) |
RSLV |
07/12/2018 |
07/12/2018 |
08/31/2018 |
| |
| 005 |
(999) |
OTHER (CELLAR) ELEV D FUSE DO NOT MATCH. (ART 240.) |
RSLV |
07/12/2018 |
07/12/2018 |
08/31/2018 |
| |
| 006 |
(315) |
CONDUCTORS NOT PROPERLY IDENTIFIED (CELLAR) ELEVATOR C CONDUCTORS NOT IDENTIFIED (ART 200.6/210.5) |
RSLV |
08/06/2018 |
08/06/2018 |
08/31/2018 |