NYC Department of Buildings
Electrical Application Details for App #: B406466
Premises: 801 PARK PLACE BROOKLYN BIN: 3330794     Block: 1233   Lot: 26
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 760 PROSPECT PL Census Tract:   317.01 Health Area:  2900
GROUND FLOOR Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11216 Community Board:   308
Special Place Name:   K138
DOB Cross Street(s):   ROGERS AVENUE,    NOSTRAND AVENUE
Status:   C - JOB IS SIGNED OFF 08/23/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/27/2016 11:05 AM
Application Entered:   01/27/2016 Job Start Date:   01/27/2016
Last Change:   08/23/2017 Job End Date:   01/31/2016
Appointment Status:   
Last Inspection By:   BANYA, E       On     08/22/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011028 Licensee Name: WILLIAM NIEVES
Firm: 002945 Firm Name: CHARAN ELEC'L ENTERP'S IN
Firm Phone: 718-706-9612  Firm Address: 9-11 40TH AVENUE LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $135.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   W - School
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ALEXANDER ANASTASIA
Owner Business Name: DOE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  3/0 WIRE
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  200 AMPS
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND                       
Buildings Total                       
Total Units : 1 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 05/31/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INSTALL NEW PANEL IN THE KITCHEN

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B406466
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/21/2016 10/21/2016 EID N (20) (0) Y
INSPECTION COMMENTS: CALLED CONTRACTOR. WAITED. NO ONE SHOWED
 
(2) 11/17/2016 11/19/2016 CLC N (60) (0) Y
INSPECTION COMMENTS: NO ACCESS CONTRACTOR NO SHOW
 
(3) 01/05/2017 01/09/2017 CJE N (38) (0) Y
INSPECTION COMMENTS: CONTRACTOR NO SHOW.
 
(4) 05/30/2017 05/31/2017 FDY V (60) (3)
INSPECTION COMMENTS: THE CONTRACTOR CUT STRANDS OFF THE 3/0 TO RETRO-FIT THE WIRES INTO THE LUGS AT THE FUSES IN THE DISCONNECT IN THE BASEMENT ELECTRICAL ROOM. THE WIRE IS NO LONGER LISTED FOR SUCH USE.
 
(5) 08/22/2017 08/23/2017 EBA C R (30) (0)
INSPECTION COMMENTS: VIOLATIONS REMOVED

OBJECTION FOR APPLICATION #: B406466
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(BASEMENT) 240.6 FUSES ARE NOT THE SAME AMPERE RATING.
RSLV 05/30/2017 05/30/2017 08/22/2017
 
002 (999) OTHER
(BASEMENT)240.6 FUSES ARE NOT SIZED FOR 200 AMP PANEL AS NOTED ON THEAPPLICATION.
RSLV 05/30/2017 05/30/2017 08/22/2017
 
003 (999) OTHER
(BASEMENT)110.2 THE 3/0 CONDUCTORS HAVE BEEN ALTERED AND ARE NO LONGERAPPROVED FOR THE AMPERE RATING IN TABLE 310.16.
RSLV 05/30/2017 05/30/2017 08/22/2017