BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B406389
Premises: 505 ST MARKS AVENUE BROOKLYN BIN: 3028319     Block: 1149   Lot: 72
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 505 ST MARKS AV Census Tract:   305
ENTIRE Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11238 Community Board:   308
Related Job Number:    320374126
DOB Cross Street(s):   CLASSON AVENUE,    FRANKLIN AVENUE SHUTTLE LINE
Status:   C - JOB IS SIGNED OFF 05/10/2016
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   01/25/2016 Job Start Date:   12/07/2016
Last Change:   05/10/2016 Job End Date:   12/31/2016
Appointment Status:   
Last Inspection By:   ROBINSON HEATH       On     03/09/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  

License #: 010996 Licensee Name: YITZCHAK GELB
Firm: 003314 Firm Name: CHAIM ELEC. CORPORATION
Firm Phone: 718-677-1040  Firm Address: 2920 AVENUE J BROOKLYN NY 11210 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
8 - BOILER/BURNER WIRING
L - LIGHTING WORK
Total Fee:  $5,040.00
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  320374126
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   52704     Submittal #: 14A0694  
Owner / Occup: YOSI COHEN
Owner Business Name: 505 ST.MARKS AVE REALTY L
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  1X400A (FIRE PUMP)
D. 601 Up to 1200 AMPS  1  1X800A (HOUSE)
E. Over 1200 AMPS  1  1X300A (TENANT)
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  150  147 APT;1 FIRE PUMP;2ELEV
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  HOUSE PNLS
D. Over 250 MCM  10  10SETS 350MCM@METER BANKS
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  147  APTS
C. 3 Phase Up to 225 AMPS  2  HOUSE
D. 3 Phase Over 225 AMPS  2  HOUSE
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  1  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    152  64    36  152  75     
BAS    227  232  17  94  227         
001    180  417  36  128  180  32  32         
002    190  472  41  143  190  36  36         
003    190  472  41  143  190  36  36         
004    190  472  41  143  190  36  36         
005    190  472  41  143  190  36  36         
006    190  472  41  143  190  36  36         
007    133  474  41  142  133  32  32         
008    133  474  41  142  133  32  32         
ROF        10  20         
Buildings Total 1778  4026  340  1257  1778     371     12      
Total Units : 9562 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 147 #4-Wire 1 #10-Wire 1
Existing Meters 0 + New Meters 149 - Removed Meters 0 = Total Meters 149

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 01/25/2016 Notice:  
Power Issued: 01/25/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B406389
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/22/2016 02/23/2016 DIT J (42) (0) Y
INSPECTION COMMENTS: DID NOT HAVE ADVISORY BOARD DRAWING AT TIME OF INSPECTION ,SERVICE NOT INSPECTED. ONLY INSPECT 8 TO 5 FLOOR.
 
(2) 03/09/2016 03/10/2016 HRB C (100) (0) Y
INSPECTION COMMENTS: PASSED




If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.