BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B404225
Premises: 380 ST JOHNS PLACE BROOKLYN BIN: 3029520     Block: 1176   Lot: 23
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 380 SAINT JOHNS PL Census Tract:   215 Health Area:  2720
APT 2R Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11238 Community Board:   308
DOB Cross Street(s):   UNDERHILL AVENUE,    WASHINGTON AVENUE
Status:   C - JOB IS SIGNED OFF 05/12/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/01/2015 3:47 PM
Application Entered:   12/01/2015 Job Start Date:   12/01/2015
Last Change:   05/12/2016 Job End Date:   12/01/2016
Appointment Status:   
Last Inspection By:   JEFFERSON, CHARLES       On     05/10/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010255 Licensee Name: THOMAS ZIMMERMAN
Firm: 004025 Firm Name: FIRST QUALITY ELECT CORP
Firm Phone: 718-797-3518  Firm Address: 75 HUNGTINGTON STREET BROOKLYN NY 11231 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $87.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: YOEL TEITELBAUM
Owner Business Name: N/A
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002    10  25  10               
Buildings Total 10  25  10                  
Total Units : 49 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 04/18/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B404225
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/14/2016 04/18/2016 CJE V (47) (3)
INSPECTION COMMENTS: CORRECT ALL OBJECTIONS.
 
(2) 05/10/2016 05/12/2016 CJE C R (22) (0)
INSPECTION COMMENTS: ALL OBJECTIONS REMOVED.

OBJECTION FOR APPLICATION #: B404225
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
(FLOOR: 002) RECEPTACLES IN HALL WAY NOT WORKING. AMEND 110.2(A)
RSLV 04/14/2016 04/14/2016 05/10/2016
 
002 (999) OTHER
(FLOOR: 002) BACK ROOM ON LEFT GAPS AROUND RECEPTACLE. ART. 314.21
RSLV 04/14/2016 04/14/2016 05/10/2016
 
003 (999) OTHER
(FLOOR: 002)BATHROOM AND KITCHEN COUNTER TOP RECEPTACLE OUTLETS BOX SET TO FARBACK IN WALL. ART 314.20
RSLV 04/14/2016 04/14/2016 05/10/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.