BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B402942
Premises: 317 HUMBOLDT STREET BROOKLYN BIN: 3427038     Block: 2777   Lot: 25
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 317 HUMBOLDT ST Census Tract:   495 Health Area:  0800
BSMT, 1ST, 2ND, 3RD, 4TH, ROOF Admin Area:   B - BROOKLYN Inspection Area:   B
BROOKLYN, NY 11211 Community Board:   301
Related Job Number:    320627639
DOB Cross Street(s):   POWERS STREET,    AINSLIE STREET
Status:   C - JOB IS SIGNED OFF 08/05/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/30/2015 5:13 PM
Application Entered:   10/30/2015 Job Start Date:   11/02/2015
Last Change:   08/05/2016 Job End Date:   03/25/2016
Appointment Status:   
Last Inspection By:   RAMJAG, BUDRAM       On     07/28/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012463 Licensee Name: DIMITRIOS K TOMBORIS
Firm: 004270 Firm Name: CAD ELECTL CONTNG SVC CO
Firm Phone: 718-353-3654  Firm Address: 7-16 COLLEGE POINT BLVD COLLEGE POINT NY 11356 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
8 - BOILER/BURNER WIRING
T - TEMPORARY LIGHT & POWER
Total Fee:  $822.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOSEPH CAPUTO
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  30 AMP ALARM
B. 101 Up to 200 AMPS  1  200 AMP P L P
C. 201 Up to 600 AMPS  1  400 AMP ALL APT
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  7  100AMP
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  3/0
D. Over 250 MCM  1  500 M C M
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  7  100AMP
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  200AMP
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  7  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    30  15    11  30             
001    51  48    16  51             
002    49  46    16  49             
003    49  46    16  49             
004    28  38    13  28             
ROF      14  14         
Buildings Total 212  200    75  212     14           
Total Units : 713 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 7 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 8 - Removed Meters 0 = Total Meters 8

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 10/30/2015 Notice: 1 - FIRST NOTICE 07/12/2016
Power Issued: 10/30/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  NEW 7 UNIT BUILDING

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B402942
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/08/2016 07/12/2016 CCH V (70) (8)
INSPECTION COMMENTS: NOTE NOT FINAL APT NO DIRECTORY
 
(2) 07/28/2016 07/29/2016 BUR C R (60) (0)
INSPECTION COMMENTS: OBJECTION RESOLVED

OBJECTION FOR APPLICATION #: B402942
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(ALL FLOORS) THROUGHOUT
RSLV 07/08/2016 07/08/2016 07/28/2016
 
002 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(ALL FLOORS) SMOKE DETECTOR
RSLV 07/08/2016 07/08/2016 07/28/2016
 
003 (999) OTHER
(ALL FLOORS) ROOF + PORCH NOT W/R 406.8
RSLV 07/08/2016 07/08/2016 07/28/2016
 
004 (999) OTHER
(ALL FLOORS) BUBBLE COVER 406.8
RSLV 07/08/2016 07/08/2016 07/28/2016
 
005 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(BASEMENT) M I G B MISSING BONDING SCREW 400 AMP
RSLV 07/08/2016 07/08/2016 07/28/2016
 
006 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(BASEMENT) NO M I G B FUSE ALARM BOX
RSLV 07/08/2016 07/08/2016 07/28/2016
 
007 (999) OTHER
(BASEMENT) 12/3 NOT 2 POLE 210.4
RSLV 07/08/2016 07/08/2016 07/28/2016
 
008 (999) OTHER
(BASEMENT) 12/3 SAME PHASE 210.7
RSLV 07/08/2016 07/08/2016 07/28/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.