Electrical Application Details for App #: B401580
Premises: 126 INDIA STREET BROOKLYN BIN: 3413883     Block: 2540   Lot: 36
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 126 INDIA ST Census Tract:   565 Health Area:  0100
ENTIRE Admin Area:   B - BROOKLYN Inspection Area:   A
BROOKLYN, NY 11222 Community Board:   301
Related Job Number:    320766328
DOB Cross Street(s):   FRANKLIN STREET,    MANHATTAN AVENUE
Status:   C - JOB IS SIGNED OFF 10/05/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/29/2015 1:27 PM
Application Entered:   09/29/2015 Job Start Date:   09/30/2015
Last Change:   10/05/2016 Job End Date:   09/30/2016
Appointment Status:   
Last Inspection By:   ROBINSON HEATH       On     09/30/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012008 Licensee Name: JAROSLAW K KURACH
Firm: 003679 Firm Name: BELMONT ELECTRICAL, INC
Firm Phone: 646-484-6641  Firm Address: 42 WEST 38TH STREET, STE 503 NEW YORK NY 10018 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $564.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JAROSLAW MORAWIEC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  100 AMP
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  400 AMP
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  9  3#2 THHN BX
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  4-350MCM
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  9  20CKT
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                 
001    30  20    10  30         
002    30  20    10  30         
003    30  20    10  30         
004    30  20    10  30         
ROF             
Buildings Total 126  87    47  126              
Total Units : 395 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 9 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 9 - Removed Meters 0 = Total Meters 9

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 09/29/2015 Notice: 1 - FIRST NOTICE 08/25/2016
Power Issued: 09/29/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B401580
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/05/2016 08/05/2016 DEX V (85) (8)
INSPECTION COMMENTS: RESOLVE DISPUTES FOR SIGN OFF
 
(2) 08/24/2016 08/25/2016 EBA V Y (40) (1)
INSPECTION COMMENTS: NOT ALL VIOLATIONS REMOVED , NEW GIVEN
 
(3) 09/30/2016 09/30/2016 HRB C R (45) (0)
INSPECTION COMMENTS: PASSED

OBJECTION FOR APPLICATION #: B401580
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (129) SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE
(BASEMENT) PLP SERVICE SWITCH NEUTRAL NOT BONDED TO PANEL ENCLOSURE
RSLV 08/05/2016 08/05/2016 08/24/2016
 
002 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
(BASEMENT) GROUND RACEWAY NOT GROUNDED
RSLV 08/05/2016 08/05/2016 08/24/2016
 
003 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(BASEMENT) 3/0 WIRE FUSED AT 400 AMP SERVICE SWITCH
RSLV 08/05/2016 08/05/2016 09/30/2016
 
004 (279) WATER METER JUMPER IS MISSING/IMPROPER
(BASEMENT) NO WATER JUMPER INSTALLED
RSLV 08/05/2016 08/05/2016 08/24/2016
 
005 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(BASEMENT) GROUND WIRE UNDER SIZED
RSLV 08/05/2016 08/05/2016 08/24/2016
 
006 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(BASEMENT) APARTMENT 2 SMOKE DETECTOR NOT AFCI PROTECTED
RSLV 08/05/2016 08/05/2016 08/24/2016
 
007 (151) AIR COND/REFRIG EQUIPMENT NOT PROPERLY MARKED/SIZED/INSTALLED
(ROOF) AC NOT LABLED ON ROOF
RSLV 08/05/2016 08/05/2016 08/24/2016
 
008 (307) NO RECEPTACLE OUTLET WITHIN 25 FEET FOR HVAC EQUIPMENT
(ROOF) NO AC OUTLET 25 FEET TO COMPRESSORS ON ROOF
RSLV 08/05/2016 08/05/2016 08/24/2016
 
009 (999) OTHER
(BASEMENT)LOW VOLTAGE WIRES IN SERVICE ROOM 110.25 / ADMINISTRATIVE
RSLV 08/24/2016 08/24/2016 09/30/2016