BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B400358
Premises: 1001 OCEAN AVENUE BROOKLYN BIN: 3120259     Block: 5206   Lot: 41
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 1001 OCEAN AV Census Tract:   516.01 Health Area:  7210
CELLAR Admin Area:   B - BROOKLYN Inspection Area:   K
BROOKLYN, NY 11226 Community Board:   314
DOB Cross Street(s):   DITMAS AVENUE,    NEWKIRK AVENUE
Status:   C - JOB IS SIGNED OFF 05/11/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/31/2015 10:18 AM
Application Entered:   08/31/2015 Job Start Date:   09/01/2015
Last Change:   05/11/2016 Job End Date:   02/27/2016
Appointment Status:   
Last Inspection By:   DALTON HENLON       On     04/19/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012301 Licensee Name: AARON LEBOVITS
Firm: 004070 Firm Name: METRO ELEC'L CONTRS, INC
Firm Phone: 718-439-7466  Firm Address: 218 HAMILTON AVENUNE BROOKLYN NY 11231 

Other Licensees and Firms:
License # Licensee Name Firm # Firm Name Type
012302 WEBER, MAYER 004070 METRO ELEC'L CONTRS, INC RESPONSIBLE REP

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $690.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: OCEAN NEWKIRK LLC
Authorized Representative:  JACK LEFKOWITZ
Relationship To Owner:   AGENT


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  600 AMP.
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  2  350 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  23  6-3 BX, APT.
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  100 AMP. PANEL PLP
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 23 #4-Wire 1 #10-Wire 0
Existing Meters 24 + New Meters 24 - Removed Meters 24 = Total Meters 24

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 08/31/2015 Notice: 1 - FIRST NOTICE 03/10/2016
Power Issued: 08/31/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B400358
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/08/2016 03/10/2016 CJH V (46) (4)
INSPECTION COMMENTS: APARTMENTS NO INSPECTED. RE-INSPECT ALL WORK
 
(2) 04/19/2016 04/26/2016 DAH C R (1) (0)
INSPECTION COMMENTS: VIOLATIONS RESOLVED

OBJECTION FOR APPLICATION #: B400358
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(CELLAR) NO PLAQUE PROVIDED FOR SVC SWITCH 230.2E
RSLV 03/08/2016 03/08/2016 04/19/2016
 
002 (999) OTHER
(CELLAR) SVC SWITCH CONDUCTOR AS NO MFG LISTED 110.2
RSLV 03/08/2016 03/08/2016 04/19/2016
 
003 (999) OTHER
(CELLAR) DISSIMILAR 600AMP FUSES 110.2
RSLV 03/08/2016 03/08/2016 04/19/2016
 
004 (999) OTHER
(CELLAR) FEEDER CONDUCTOR NOT PROPERLY TAP 240
RSLV 03/08/2016 03/08/2016 04/19/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back