| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
3 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
1 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
2 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER (FLOOR: 001)001 FL PENINSULAR COUNTER TOP EXTENDED OVER 6" 210.52 C5 |
RSLV |
05/10/2016 |
05/10/2016 |
05/31/2016 |
| |
| 002 |
( 18) |
DEFECTIVE RECEPTACLES ARE IN USE (FLOOR: 002) 002 KIT COUNTER TOP RECEPT 110.2 |
RSLV |
05/10/2016 |
05/10/2016 |
05/31/2016 |
| |
| 003 |
(282) |
MINIMUM NUMBER OF SMALL APPLIANCE CIRCUITS (FLOOR: 002) 002 TWO CKT NOT PROVIDED 210.52 (B1) |
RSLV |
05/10/2016 |
05/10/2016 |
05/31/2016 |
| |
| 004 |
(283) |
SMALL APPLIANCE OUTLETS NOT PROPERLY LOCATED (FLOOR: 002) 002 WINE COOLER CKT 210.52(C5) |
RSLV |
05/10/2016 |
05/10/2016 |
05/31/2016 |
| |
| 005 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (FLOOR: 002) 002 KIT COUNTER TOP RECEPT NOT GFCI 210.8 |
RSLV |
05/10/2016 |
05/10/2016 |
05/31/2016 |
| |
| 006 |
(999) |
OTHER (FLOOR: 003) 003 BATH GFCI NOT TR 406.11 |
RSLV |
05/10/2016 |
05/10/2016 |
05/31/2016 |
| |
| 007 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (CELLAR) CELLAR PNL NOT LABELLED 408.4 |
RSLV |
05/10/2016 |
05/10/2016 |
05/31/2016 |
| |
| 008 |
(999) |
OTHER (CELLAR) CELLAR BATH RM CKT WITH RECEPT 210.11C3 |
RSLV |
05/10/2016 |
05/10/2016 |
05/31/2016 |
| |
| 009 |
(999) |
OTHER (ROOF) ROF AC UNITS WHT USED AS HOT 200.7 |
RSLV |
05/10/2016 |
05/10/2016 |
05/31/2016 |
| |
| 010 |
(999) |
OTHER (ROOF) ROF AC UNITS GND NOT PROPERLY SIZE 250.122 |
RSLV |
05/10/2016 |
05/10/2016 |
05/31/2016 |
| |
| 011 |
(999) |
OTHER (ROOF) ROF AC UNITS #14 IN USED 219.19 (A1) |
RSLV |
05/10/2016 |
05/10/2016 |
06/29/2016 |