Electrical Application Details for App #: B398405
Premises: 60 WATER STREET BROOKLYN BIN: 3398406     Block: 36   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 60 WATER ST Census Tract:   21 Health Area:  1000
DOCK STREET Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11201 Community Board:   302
Special Place Name:   PS 611
DOB Cross Street(s):   DOCK STREET,    MAIN STREET
Status:   C - JOB IS SIGNED OFF 09/14/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/16/2015 3:15 PM
Application Entered:   07/16/2015 Job Start Date:   07/20/2015
Last Change:   09/14/2017 Job End Date:   12/20/2016
Appointment Status:   
Last Inspection By:   WEISBART, F.       On     09/13/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011319 Licensee Name: KWOK L LI
Firm: 003485 Firm Name: A TECH ELEC ENTERPRISES
Firm Phone: 917-921-0620  Firm Address: 360 EAST 116TH ST., SUITE 2E INC NEW YORK NY 10029 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $778.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   W - School
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: GUS MICHAELIDES
Owner Business Name: NYCSCA
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  1  4#1/0
C. Over 1/0 to 250 MCM  2  4#3/0
D. Over 250 MCM  3  4#500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  4  
D. 3 Phase Over 225 AMPS  1  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND    50  80    25  200  50  10  80     
Buildings Total 50  80    25  200     50     80      
Total Units : 485 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 11/22/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  THIS PERMIT IS FOR PRE K SCHOOL

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B398405
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/14/2016 04/14/2016 HRB J (50) (0) Y
INSPECTION COMMENTS: CONTRACTOR MUST RE-FILE THE WHOLE JOB TO SHOW FULL BUILD OUT
 
(2) 05/17/2016 05/18/2016 HRB J (50) (0) Y
INSPECTION COMMENTS: NEED OTHER APPLICATION. NEED MORE TIME TO PERFORM INSPECTION
 
(3) 09/02/2016 09/06/2016 HRB J (55) (0) Y
INSPECTION COMMENTS: NEED TO EITHER RE-FILE OR AMEND APP TO SHOW FULL BUILD OUT
 
(4) 10/13/2016 10/13/2016 CJE V (65) (4)
INSPECTION COMMENTS: CORRECT ALL OBJECTIONS.
 
(5) 11/22/2016 11/22/2016 DAH J X (5) (0) Y
INSPECTION COMMENTS: JOB NOT COMPLETE
 
(6) 03/10/2017 03/13/2017 DIT J R (45) (0)
INSPECTION COMMENTS: NEED MORE TIME TO PERFORM INSPECTION.
 
(7) 08/11/2017 08/11/2017 EBA N (30) (0) Y
INSPECTION COMMENTS: CONTRACTOR ALREADY LEFT THE PREMISES
 
(8) 09/13/2017 09/14/2017 FWE C (30) (0) Y
INSPECTION COMMENTS: OK

OBJECTION FOR APPLICATION #: B398405
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (243) CONDUCTORS OF THE SAME CIRCUIT NOT GROUPED
(GROUND FLOOR) PANEL TP CKTS NOT PROPERLY GROUPED. ART. 300.3(B)
RSLV 10/13/2016 10/13/2016 03/10/2017
 
002 (243) CONDUCTORS OF THE SAME CIRCUIT NOT GROUPED
(GROUND FLOOR) PANEL MP CKTS NOT PROPERLY GROUPED. ART. 300.3(B)
RSLV 10/13/2016 10/13/2016 03/10/2017
 
003 (243) CONDUCTORS OF THE SAME CIRCUIT NOT GROUPED
(GROUND FLOOR) PANEL LP CKTS NOT PROPERLY GROUPED. ART. 300.3(B)
RSLV 10/13/2016 10/13/2016 03/10/2017
 
004 ( 45) FIXTURE NOT INSTALLED IN AN APPROVED MANNER
(GROUND FLOOR)ELECTRIC DISCHARGE FIXTURES QUICK DISCONNECT MEANS NOT PROVIDED.ART. 410.130(G1)
RSLV 10/13/2016 10/13/2016 03/10/2017