BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B397955
Premises: 1114 64 STREET BROOKLYN BIN: 3141995     Block: 5745   Lot: 11
   
Application Completed and Certified

Filed: 1114 64 ST Census Tract:   212 Health Area:  8020
BASEMENT AND 2ND FLOOR Admin Area:   B - BROOKLYN Inspection Area:   M
BROOKLYN, NY 11219 Community Board:   310
DOB Cross Street(s):    11 AVENUE,    12 AVENUE
Status:   C - JOB IS SIGNED OFF 10/28/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/07/2015 10:48 PM
Application Entered:   07/07/2015 Job Start Date:   07/08/2015
Last Change:   10/28/2015 Job End Date:   05/08/2016
Appointment Status:   
Last Inspection By:   THOMAS, PATRICIA       On     10/07/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012398 Licensee Name: WEN BIN CEN
Firm: 004190 Firm Name: R & T ELECTRICAL CORP
Firm Phone: 718-526-6888  Firm Address: 36-03B COLLEGE POINT BLVD BSMNT FLUSHING NY 11354 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $118.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   B - Two Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ZHU ZHANG
Owner Business Name: N/A
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  3  100AMPS #2WIRE
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  100AMPS #2 WIRE SEC2#6FDR
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  2  16 CIRCUIT PANEL
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002    10  15  10  10             
Buildings Total 10  15  10  10                
Total Units : 48 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 3 #4-Wire 0 #10-Wire 0
Existing Meters 2 + New Meters 3 - Removed Meters 2 = Total Meters 3

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/07/2015 Notice: 1 - FIRST NOTICE 10/01/2015
Power Issued: 07/07/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  ADDING HALLWAY METER AND WIRING 2ND FLOOR

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B397955
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/22/2015 10/01/2015 JTE A E (40) (3) Y
INSPECTION COMMENTS: NONE
 
(2) 10/07/2015 10/15/2015 PAT C R E (20) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B397955
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT-BRKE'S IN USE NOT LISTED FOR PANEL MODEL 110.3(B)
RSLV 09/22/2015 09/22/2015 10/07/2015
 
002 (999) OTHER
BSMT-12-3 CKT REQ'D HANDLE TIE 210.4(B)
RSLV 09/22/2015 09/22/2015 10/07/2015
 
003 ( 19) DEFECTIVE WIRING IS IN USE
BSMT-1ST FL-PANEL TWO DIFF CKTS FROM 2 DIFF 12-3'S ARE BEING SPLICEDTOGETHER
RSLV 09/22/2015 09/22/2015 10/07/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.